IONPURE
®
G2 DISPLAY BOARD – IP-POWERDSP-G2
IP-POWERDSP-G2MAN Rev 1
Page 13 of 25
3.2
Menu Structure
Figure 8: Menu Tree Structure
OVERVIEW
: this is the startup screen. It displays 3 channels at a time and shows the CEDI
module’s identification number (selected on the G2 Power Controller via switch SW2), DC
output volts, DC output current and module resistance in ohms. Unused channels are
represented with a line of asterisks (*). Resistance values above 999.9 are represented with
“***HI”. When the DC output current is zero, resistance will be represented with “----“ to
indicate that resistance can not be measured.
Channels 1, 2 and 3 are displayed upon startup of the unit. Pressing the UP or DOWN arrows
will scroll through all 16 channels.
A blinking module number indicates where the cursor is. Pressing the ENTER key will access
the RUN submenu of the CEDI module selected with the cursor.
A blinking row indicates and alarm condition for a specific power controller. The alarm type
can be identified under the ALARMS submenu.