G2 DISPLAY BOARD – IP-POWERDSP-G2
IP-POWERDSP-G2MAN Rev 1
Page 15 of 25
48 hours of cumulative operation from the initial startup. Resistance values
above 999.9 are represented as “***HI”.
PAGE 2:
Figure 11: RUN Screen – Page 2
Ohms chg%
: percentage of change in CEDI module resistance from initial
(Ohms init) to present (Ohms pres). Positive values represent an increase in
resistance and negative values represent a decrease in resistance, in reference
to the initial value.
V AC in
: actual AC input voltage to the selected power controller. If this value is
higher than 726 VAC, a high AC input alarm will trigger.
A AC in
: actual AC input current drawn by the selected power controller.
Power(kW)
: actual power consumption (Volts DC x Amps DC) in kilowatts of the
selected CEDI module.
PAGE 3:
Figure 12: RUN Screen – Page 3