6. Operation
DEPOLOX® Pool Compact
52
EN
Chlorine measurement parameters
pH measurement parameters
ORP (Redox) measurement parameters
Measurement
Range:
1, 2, 3, 5 and 10 mg/l
Unit:
mg/l, ppm
Measurement filter:
off/low/middle/strong
Limits
Limits value I
Max:
within range
Min:
within range
Hysteresis:
0.01 to 0.25
Limits value II
Max:
within range
Min:
within range
Hysteresis:
0.01 to 0.25
Controller
Setpoint:
within range
Proportional factor Xp:
1 bis 1000
Integral action time Tn:
0 bis 100.0 min
Auto tune:
Starten
Dead time Tu:
1 bis 480 min
Rise time Ts:
1 to 60 min
Dosing
Actuator:
Dosing pump 2P, solenoid pump,
positioner wo. Ym, analog output mA,
dosing contact
Cycle period Tp:
10 to 180 s
max. ulse:
100/120/140/160/180
Running time Ty:
10 to 180 s
Hysteresis:
0.01 to 0.50
min. duty cycle:
00:00 to 10:00 h
max. off-duty cycle:
00:00 to 10:00 h
Reset dosing average
Sampling time Ta
Measurement
Upper range:
pH 8 to 14
Lower range:
pH 0 to 6
Measurement filter:
off/low/middle/strong
Limits
Limits value I
Max:
within range
Min:
within range
Hysteresis:
0.01 to 0.25
Limits value II
Max:
within range
Min:
within range
Hysteresis:
0.01 to 0.25
Controller
Setpoint :
within range
Proportional factor Xp
Integral action time Tn
Dosing
Actuator:
Dosing pump 2P, dosing pump 3P,
solenoid pump 2P, solenoid pump 3P, posi-
tioner wo. Ym, analog output 2P, analog out-
put 3P, dosing contact
Direction:
Acid/Alkali
Cycle period Tp:
10 to 180 s
max. pulse:
100/120/140/160/180
Running time Ty:
10 to 180 s
Hysteresis:
0.01 to 0.50
min. duty cycle:
00:00 to 10:00 h
max. off-duty cycle:
00:00 to 10:00 h
Reset dosing average
Sampling time Ta
Measurement
Upper range:
600/700/800/900/1000
Lower range:
0/100/200/300/400
Measurement filter:
off/low/middle/strong
Limits
Limits value
Max:
within range
Min:
within range
Hysteresis:
1 to 25
Limits value II
Max:
within range
Min:
within range
Hysteresis:
1 to 25