DEPOLOX® Pool Compact
4. Interfaces
33
EN
400314
UINT32
4
R
Error code pH/Fluoride (Ch.2) Coding see Reg. 400310
400318
UINT32
4
R
Error code ORP (Redox) (Ch.3) Coding see Reg. 400310
400326
UINT32
4
R
Error code temperature (Ch.5) Coding see Reg. 400310
(Ch.1) Chlorine - Controller parameter
401000
FLOAT
4
RW
Setpoint (W)
in the measuring range
401002
FLOAT
4
RW
P-element(Xp)
0 - 1000%
401004
FLOAT
4
RW
I-element (Tn)
0.0 - 100.0 min
0 = Tn inactive
(Ch.2) pH - Controller parameter
401006
FLOAT
4
RW
Setpoint (W)
in the measuring range
401008
FLOAT
4
RW
P-element (Xp)
0 - 1000%
401010
4
--
(Ch.3) Reserved
401012
401014
401018
(Ch.4) Conductivity - Controller parameter
401018
FLOAT
4
RW
Setpoint (W)
in the measuring range
401020
FLOAT
4
RW
P-element(Xp)
0 - 1000%
401022
FLOAT
4
RW
I-element (Tn)
0.0 - 100.0 min
0 = Tn inactive
(Ch.1) Chlorine - Limits
401050
FLOAT
4
RW
Min. value 1
Lower range - Max 1
401052
FLOAT
4
RW
Max. value 1
Min 1 - Upper range
401054
FLOAT
4
RW
Hysteresis valuve 1
1 - 25 Digit
401056
FLOAT
4
RW
Min. value 2
Lower range - Max 2
401058
FLOAT
4
RW
Max. value 2
Min 2 - Upper range
401060
FLOAT
4
RW
Hysteresis value 2
1 - 25 Digit
(Ch.2) pH - Limits
401062
FLOAT
4
RW
Min. value 1
Lower range - Max 1
401064
FLOAT
4
RW
Max. value 1
Min 1 - Upper range
401066
FLOAT
4
RW
Hysteresis value 1
1 - 25 Digit
401068
FLOAT
4
RW
Min. value 2
Lower range - Max 2
401070
FLOAT
4
RW
Max. value 2
Min 2 - Upper range
401072
FLOAT
4
RW
Hysteresis value 2
1 - 25 Digit
Modbus
Register
Bit
Type
No.
Byte
Access
Designation
Description