46
ENGLISH
F20
0
100
%
60
60
Speed 3 of the evaporator fan (in terms of percentage of
maximum speed: if the F0 parameter is set to 3 only); see
paragraph 6.12 “cooling and freezing intensity”
F21
0
100
%
80
80
Speed 4 of the evaporator fan (in terms of percentage of
maximum speed; if the F0 parameter is set to 3 only); see
paragraph 6.12 “cooling and freezing intensity”
F22
0
100
%
100
100
Speed 5 of the evaporator fan (int erms of percentage of
maximum speed; if the F0 parameter is set to 3 only); see
paragraph 6.12 “cooling and freezing intensity”
F23
1
5
- - - -
5
5
Speed at which the evaporator fan is switched on during
preservation after cooling
1 = speed set with the F18 parameter (speed 1)
2 = speed set with the F19 parameter (speed 2)
3 = speed set with the F20 parameter (speed 3)
4 = speed set with the F21 parameter (speed 1)
5 = speed set with the F22 parameter (speed 5)
F24
1
5
- - - -
5
5
Speed at which the evaporator fan is switched on during
preservation after freezing
1 = speed set with the F18 parameter (speed 1)
2 = speed set with the F19 parameter (speed 2)
3 = speed set with the F20 parameter (speed 3)
4 = speed set with the F21 parameter (speed 1)
5 = speed set with the F22 parameter (speed 5)
F25
0
30
min
0
0
Delayed evaporator fan switching on from the compressor
switching on to the cooling and freezing starting
Par.
Min.
Mas.
Unità
Default
Default
Digital inputs
i0
0
2
- - - -
1
1
Effect caused by the door opening, i.e.by the activation of the
micro input port (13)
0 = no effect
1 = both compressor and evaporator fan are switched off and
the cell light is switched on, after the time set with the i2
parameter has passed by, system will show the flashing
“id” code and buzzer will be sounding (until the closing of
the door); see also the F15 parameter (14)
2 = evaporator fan is switched off and the cell light is switched on,
after the time set with the i2 parameter has passed by,
system will show the flashing “id” code and buzzer will be
sounding (until the closing of the door); see also the F15
parameter.
i1
0
1
- - - -
1
1
Type of contact on the micro input port
0=normally open (active input with closed contact)
1=normally closed (active input with open contact)
i2
-1
120
min
5
5
Delayed door open alarm signal (code “id”); after the time set
with parameter has passed by, both compressor and
evaporator fan are switched off.
-1 = alarm is not reported
i5
0
1
- - - -
1
1
Effect caused by the high pressure input activation
0 = no effect
1 = both compressor and evaporator fan are switched off and
the condenser fan is switched on, after the time set with
the i7 parameter has passed by, system will show the
flashing “HP” code and buzzer will be sounding (until
input is deactivated).
i6
0
1
- - - -
0
0
iType of contact on the high pressure input
0=normally open (active input with closed contact)
1=normally closed (active input with open contact)
i7
-1
240
s
5
5
Delayed high pressure alarm signal (code “HP”)
-1 = alarm is not reported
i8
0
1
- - - -
0
0
Type of contact on the low pressure input
0 =normally open (active input with closed contact)
1 =normally closed (active input with open contact)