45
ENGLISH
A5
0
1
- - - -
1
1
Enable maximum temperature alarm (code “AH”)
1 = yes
A7
0
240
min
30
30
Delayed temperature alarm (code “AL” and code “AH”)
A8
0
240
min
30
30
Delayed maximum temperature alarm (code “AH”) from the end
of evaporator fan stop and from the preservation starting
A10
0
240
min
5
5
duration of power supply interruption such to cause the storage
of the power supply failure alarm (code “PF”) when it is reset
0 = alarm will not be signalled
AA
0
240
s
5
5
Duration of buzzer activation when cooling and feezing are over
A11
1
15
°C / °F (1)
2
2
Differential of the A1 and A4 parameters
A13
0
1
- - - -
1
1
storage of temperature cooling alarm or temperature freezing not
completed within time limit (code “tiM”)
1 = yes
A14
- - - -
- - - -
- - - -
- - - -
- - - -
reserved
Par.
Min.
Mas.
Unità
Default
Default
Evaporator and Condenser fan
F0
0
3
- - - -
1
1
Evaporator fan activity during precooling, cooling and freezing
(is the parameter is set to 3, this shall apply even during
preservation)
0 = off , with digital-type control signal i.e. through digital output
K3
1 = on, with digital-type control signal, i.e. through digital output
K3; see also the F16 and F17 parameters
2 = parallel to compressor , with digital-type control signal i.e.
through digital output K3; see also the F9 and F17 parameters
3 = with analog-type control signal , i.e. through PWM-like digital
output and phase cutoff output of speed regulator for single-
phase fan EVDFAN1
(to be ordered separately); see also the F18, F19, F20, F21,
F22, F23 e F24 parameters
F1
-99
99
°C / °F (1)
10
10
Evaporator temperature above which the evaporator fan is
switched off during preservation (if the F0 and/or F2 parameters
are set to 3); see also the F8 parameter (11)
F2
0
3
- - - -
2
2
evaporator fan activity during preservation (if the F0 parameter is
set to values different from 3 only)
0 = off
1 = on
2 = parallel to compressor; see also the F9 parameter
3 = on ; see also the F1 parameter
F3
0
15
min
0
0
Duration of the evaporator fan stop (during the evaporator fan
stop the compressor can be switched on, the defrost output is
deactivated and the evaporator fan is off)
F8
1
15
°C / °F (1)
2
2
Differential of the F1, F16 e F17 parameters
F9
0
240
s
15
15
Delayed evaporator fan switching off since the compressor
switching off (if the F0 and / or F2 parameters are set to 2 only)
F11
0
99
°C / °F (1)
15
15
condenser temperature above which the condenser fan is
switched on (in terms of “F11 + differential and provided that
compressor is switched off) ; see also the F12 parameter (4)
(12)
F12
0
240
s
30
30
Delayed condenser fan switching off since the compressor
switching off (if the P5 parameter is set to 0 only)
F15
0
240
s
0
0
Delayed evaporator fan since the closing of the door i.e.: since
the deactivation of the micro input door.
F16
-99
99
°C / °F (1)
70
70
evaporator temperature above which the evaporator fan is
switched off during precooling, cooling and freezing (if the F0
parameter is set to 1 only); see also the F8 parameter (11)
F17
-99
199
°C / °F (1)
90
90
cell temperature above which the evaporator fan is switched off
during precooling, cooling and freezing (if the F0 parameter is
set to 1 or 2 only); see also the F8 parameter
F18
0
100
%
20
20
Speed 1 of the evaporator fan (in terms of percentage of
maximum speed; if the F0 parameter is set to 3 only); see also
paragraph 6.12 “cooling and freezing intensity”
F19
0
100
%
40
40
Speed 2 of the evaporator fan (in terms of percentage of
maximum speed: if the F0 parameter is set to 3 only); see
paragraph 6.12 “cooling and freezing intensity”