43
ENGLISH
P3
0
3
- - - -
1
1
Number of sensors of core probe
0 = core probe not enabled
1 = 1 (core probe1)
2 = 2 (core probe 1 and core probe 2)
3 = 3 (core probe 1, core probe 2 and core probe 3)
P4
0
1
- - - -
1
1
Enable the evaporator probe
1 = yes
P5
0
1
- - - -
0
0
Enale the condenser probe
1 = yes
P8
0
1
- - - -
0
0
Display direction
0 = display is placed higher than the unit
1 = display is placed lower than the unit
Par.
Min.
Max.
Unit
Default
Default
Main Regulator
r0
1
15
°C / °F (1)
3
3
Differential of the r7, r8, r9, r10, r11 and r12 parameters
r1
1
500
min
90
90
time cooling duration
r2
1
500
min
240
240
time freezing duration
r3
-99
99
°C / °F (1)
3
3
Temperature of end-of-temperature-cooling ; temperature of end-
of-soft-phase temperature freezing (temperature taken by the
core probe); see also the r5 parameter
r4
-99
99
°C / °F (1)
-18
-18
Temperature of end-of-temperature freezing (temperature taken
by core probe) ; see also the r6 parameter
r5
1
500
min
90
90
Maximum duration of temperature cooling ; see also the r3
parameter
r6
1
500
min
240
240
Maximum duration of temperature freezing ; see also the r4
parameter
r7
-99
99
°C / °F (1)
-2
-2
Working setpoint during cooling : even working setpoint during
the soft phase of soft freezing (cell temperature) ; see also the r0
parameter
r8
-99
99
°C / °F (1)
-40
-40
Working setpoint durig freezing (cell temperature); see also the
r0 parameter
r9
-99
99
°C / °F (1)
-20
-20
Working setpoint during the hard phase of hard cooling (cell
temperature); see also the r0 prameter
r10
-99
99
°C / °F (1)
2
2
Working setpoint during preservation after cooling (cell
temperature) ; see also the r0 parameter
r11
-99
99
°C / °F (1)
-22
-22
Working setpoint during preservation after freezing (cell
temperature); see also the r0 parameter
r12
-99
99
°C / °F (1)
0
0
Working setpoint during precooling (cell temperature) ; see also
the r0 parameter
r13
-99
99
°C / °F (1)
15
15
Temperature of end-of-hard-phase of temperature hard cooling
(temperature taken by core probe)
r14
10
100
%
60
60
Duration of the hard phase of time hard cooling (in terms of
percentage of the value set with the r1 parameter); even duration
of the soft phase of time soft freezing ( in terms of percentage of
the value set with the r2 parameter)
r15
-99
199
°C / °F (1)
70
70
Temperature below which the count of the maximum duration
of temperature cooling and of temperature freezing starts
(temperature taken by core probe)
r16
0
2
- - - -
1
1
Type of runnning cycle that can be selected
0 = cooling and preservation
1 = cooling and preservation or freezing and preservation
2 = freezing and preservation
r17
0
99
°C / °F (1)
5
5
Minimum difference between “temperature taken by core probe”
and “cell temperature” to consider the first phase of the test
for checking the proper insertion of core probe successfully
completed (you should consider the difference with no sign)
0 = test will not be carried out (neither the first nor the second
phase)
r18
1
99
s
60
60
Duration of the second phase of the test for checking the proper
insertion of core probe
r19
- - - -
- - - -
- - - -
- - - -
- - - -
reserved
Par.
Min.
Mas.
Unità
Default
Default
Compressor protecting system
C0
0
240
min
1
1
Minimum time interval between the power supply restoration
after an interruption occurring during a running cycle and the
compressor switching on.
C1
0
240
min
5
5
Minimum time interval between two consecutive switching on of
compressor (3)