activated for the blocking, holding and manual cooling phases
F26
0
1
- - - -
0
evaporator fan mode during defrost
0 = off
1 = on
F27
0
100
%
10
speed 1 evaporator fan, if E7=2 or 3
F28
0
100
%
20
speed 2 evaporator fan, if E7=2 or 3
F29
0
100
%
30
speed 3 evaporator fan, if E7=2 or 3
F30
0
100
%
40
speed 4 evaporator fan, if E7=2 or 3
F31
0
100
%
50
speed 5 evaporator fan, if E7=2 or 3
F32
0
100
%
60
speed 6 evaporator fan, if E7=2 or 3
F33
0
100
%
70
speed 7 evaporator fan, if E7=2 or 3
F34
0
100
%
80
speed 8 evaporator fan, if E7=2 or 3
F35
0
100
%
90
speed 9 evaporator fan, if E7=2 or 3
F36
0
100
%
100
speed 10 evaporator fan, if E7=2 or 3
Par.
Min
Max
Unit
Default Setpoint of manual cooling and heating cycle
MC1
-99.0
99.0
°C
-5.0
cabinet temperature setpoint in manual cooling
MC2
1
10
- - - -
10
fan speed in manual cooling
MC3
0
100
%
70
humidity setpoint in manual cooling
MC4
0
5999
min
120
duration manual cooling
MH1
-99.0
99.9
°C
25.0
cabinet temperature setpoint in manual heating
MH2
1
10
- - - -
10
fan speed in manual heating
MH3
0
100
%
80
humidity setpoint in manual heating
MH4
0
5999
min
180
duration manual heating
Par.
Min
Max
Unit
Default Sanitation
SA0
0
2
- - - -
0
type of sanitation
0 = not present
1 = UV lamp
2 = ozone generator
SA1
-99.0
99.0
°C
0.0
cabinet temperature below which the sanitation cycle, if
started, is suspended
SA2
0
240
min
10
duration of sanitation cycle only if SA0=2
(see parameter E21 for resting time)
SA3
0
240
min
5
resting time after sanitation cycle if SA0=2
(if SA3=0, resting time is not taken into consideration)
Par.
Min
Max
Unit
Default Digital inputs
i0
0
2
- - - -
2
effect of the door opening, or when the door switch input is
activated
0 = no effect
1 =
the compressor and evaporator fan are switched off
(no effect on light status)
2 =
the evaporator fan is switched off (no effect on the
compressor or light status)
3 = only light switched on
4 = the compressor and evaporator fan are switched off,
the cabinet light is switched on
5 = the evaporator fan is switched off, the cabinet light is
switched on
N.B.:
- if the door is opened, the humidifier, steriliser/oxygenator
and heater are switched off