EVCO S.p.A.
Vcolor 679/689
| Installer manual ver. 1.0 | Code 144VC679I104
page 53 of 70
rr9
(1)
1
100
%
1
percentage increase for the 9th re-awakening step (out of a
total of 100%)
rr10
(1)
1
100
%
1
percentage increase for the 10th re-awakening step (out of a
total of 100%)
rL0
(1)
1
10
- - - -
4
number of steps for heater regulation for the proofing phase
rL1
(1)
1
100
%
25
percentage increase for the 1st proofing step (out of a total
of 100%)
rL2
(1)
1
100
%
50
percentage increase for the 2nd proofing step (out of a total
of 100%)
rL3
(1)
1
100
%
75
percentage increase for the 3rd proofing step (out of a total
of 100%)
rL4
(1)
1
100
%
100
percentage increase for the 4th proofing step (out of a total
of 100%)
rL5
(1)
1
100
%
1
percentage increase for the 5th proofing step (out of a total
of 100%)
rL6
(1)
1
100
%
1
percentage increase for the 6th proofing step (out of a total
of 100%)
rL7
(1)
1
100
%
1
percentage increase for the 7th proofing step (out of a total
of 100%)
rL8
(1)
1
100
%
1
percentage increase for the 8th proofing step (out of a total
of 100%)
rL9
(1)
1
100
%
1
percentage increase for the 9th proofing step (out of a total
of 100%)
rL10
(1)
1
100
%
1
percentage increase for the 10th proofing step (out of a total
of 100%)
Par.
Min
Max
Unit
Default Humidity regulator
rU0
0
1
- - - -
0
humidity management mode:
0 = with humidity probe/transducer (only if P12≠0)
1 = without humidity probe/transducer, time intervals
based on the percentage set
rU1
-99.0
99.0
°C
0.0
minimum cabinet temperature for inhibiting humidification
control
rU2
1
600
s
60
cycle time for humidifier switch-on (only for rU0 = 1, see also
rU3)
rU3
1
600
s
30
humidifier switch-on within rU2 cycle time to generate 100%
humidity in cabinet (only for rU0 = 1, see also rU2)
rU4
0
2
- - - -
0
enable humidification/dehumidification control during the
blocking, holding and manual cooling phases
0 = humidification/dehumidification control is disabled but
the value of the humidity probe is displayed (only if
P12≠0, otherwise dashes are displayed)
1 = humidification/dehumidification control is enabled (the
value of the probe is displayed only if P12≠0,
otherwise the setpoint is displayed)
2 = humidification/dehumidification control is disabled, the
value of the humidity probe is not displayed, only
three dashes
rU5
1
100
% r.H.
5
dehumidification differential
rU6
0
100
% r.H.
2
dehumidification neutral zone value
rU7
0
255
s
10
duration of dehumidification attempt with pump-down
solenoid valve
rU8
1
100
% r.H.
5
humidification differential
rU9
0
100
% r.H.
2
humidification neutral zone value