Evco Vcolor 679 Installer Manual Download Page 42

EVCO S.p.A.   

 

Vcolor 679/689

 | Installer manual ver. 1.0 | Code 144VC679E104 

page 

42

 of 

70

 

10.8

 

Dehumidification management 

Dehumidification management is only active when humidity is managed by a humidity probe/transducer (rU0 = 0). 

Dehumidification  can  be  managed  in  the  first  mode  described  below  when  configuring  proofing  and  in  both  modes  when  configuring 

retarding-proofing: 

 

-

 

using an extraction fan with “uxc=15” (in this case parameter “u3” will not be considered, irrespective of the assigned value); 

-

 

by activating the refrigeration plant (compressor and pump-down solenoid valve if fitted) with “u3 = 1” and “uxc ≠ 15”. 

Dehumidification management is deactivated with “u3 = 0” and “uxc ≠ 16”. 

 

10.8.1

 

 Extractor fan/dehumidifier management  

When  managed  by  an  extractor  fan/dehumidifier,  the  output  will  be  activated  when  the  humidity  rises  above  the  dehumidification 

neutral zone value (rU6) plus the differential value (rU5) and it is deactivated when the humidity returns to within the dehumidification 

neutral zone value. 

 

10.8.2

 

 

Management by refrigeration plant activation

 (for retarding-proofing only) 

When  pump-down  solenoid  valve  management  is  not  enabled,  the  output  will  be  activated  when  the  humidity  rises  above  the 

dehumidification neutral zone value (rU6) plus the differential value (rU5) and it is deactivated when the humidity returns to within the 

dehumidification neutral zone value. 

If,  however,  pump-down  solenoid  valve  management  is  enabled,  there  will  be  a  first  attempt  at  dehumidification  by  activating  the 

pump-down solenoid valve (to make use of the high pressure generated when the compressor is switched off), for a time period set by 

rU7. After this time has elapsed, the compressor output will be activated. 

Once the humidity returns to within the dehumidification neutral zone value, the pump-down solenoid valve will be deactivated, after 

which the compressor will be deactivated by the pump-down algorithm. 

 

10.9

 

Condenser fan management (for retarding-proofing only) 

The condenser fan is managed by assigning a value of “3” to one of the relay outputs. 

If the condenser probe is enabled (see parameters Pr1, Pr2, Pr3), the condenser fan will be activated when the condenser temperature 

rises above the value of parameter F16 plus the differential value (F16 + 2.0 °C / 4 °F), based on the configuration of parameter F18. 

The condenser fan will switch off when the condenser temperature falls below the value of parameter F16. 

If the condenser probe is not configured, the condenser fan will be activated in parallel with the compressor, while deactivation will be 

delayed for the time set by parameter F17. 

During CONDENSER OVERHEAT or COMPRESSOR LOCKED alarm, the condenser fan will stay on. 

The fans will be switched off during defrost. 

 

10.10

 

Cabinet light management 

The cabinet light will switch on/off if the door is opened or closed, if the 

 key is pressed while manual and/or automatic cycles are 

being carried out or if the controller is in the Stand-by screen. 

Switching on with the key has priority over the door switch. 

If the light is off, opening and closing the door will activate and deactivate the relative output. 

If the light has been switched on with the key, opening or closing the door will have no effect on the light (the light will stay on until it 

is switched off from the key or the controller is put in in stand-by).  

 

10.11

 

Door frame management (for retarding-proofing only) 

The  door  frame  heater  output,  if  configured,  is  activated  when  the  cabinet  temperature  goes  below  parameter  u5;  it  is  deactivated 

when the cabinet temperature is higher than u5+rC0. 

 

10.12

 

On/stand-by relay configuration 

This output does not depend on any regulation; it is activated when the controller is ON and deactivated when the controller is in 

STAND-BY. 

 

10.13

 

Output testing 

The password to enter this mode is -19. 

In  this  mode,  all  the  outputs  (digital  and  analogue)  in  the  controller  can  be  manually  activated/deactivated  independently  of  the 

regulation in progress. Every output can be activated/deactivated individually. 

Summary of Contents for Vcolor 679

Page 1: ...689 Installer manual ver 1 0 Code 144VC679E104 page 1 of 70 Vcolor 679 689 Controllers for retarding proofing or proofing cabinets and rooms with customised graphic skin ENGLISH INSTALLER MANUAL ver...

Page 2: ...using the device and take all the prescribed precautions Keep this document with the device for future consultation Only use the device in the ways described in this document Do not use the device as...

Page 3: ...Pre cooling for retarding proofing only 36 9 2 Temperature regulation 36 9 3 Humidity regulation 37 10 LOAD MANAGEMENT 39 10 1 ON OFF variable speed compressor management for retarding proofing only 3...

Page 4: ...for proofing and cooling pre cooling heating for retarding proofing The controller s innovative programmable platform gives manufacturers the freedom to personalise the graphic skin and programmes an...

Page 5: ...y the control module Powered by an external transformer 12VAC 20VA Optional modules 115 230 Vac 230 Vac 230 Vac Analogue inputs Cabinet probe PTC NTC Evaporator probe PTC NTC Condenser probe PTC NTC H...

Page 6: ...ifier 8 A 8 A Configurable K4 default dehumidifier 8 A 8 A Configurable K5 default defrost 8 A 8 A Configurable K6 default heater 16 A 16 A Configurable K7 default steam generator 16 A 16 A Configurab...

Page 7: ...ation see section 16 TECHNICAL SPECIFICATIONS The table below lists the purchasing codes of the available models Purchasing codes Models with PWM output Vcolor 679 M control module 5 user interface EV...

Page 8: ...s for horizontal operation and have capacitive colour TFT touch screen graphic displays 2 2 Control module measurements and installation Installation of the control module is on a flat surface with sp...

Page 9: ...of 70 Vcolor 679 689 L interface 2 4 User interface installation Depending on the model installation can be flush from behind the panel with threaded studs not provided welded to hold it in place semi...

Page 10: ...ts See section 16 TECHNICAL SPECIFICATIONS Do not install the device close to heat sources heaters hot air ducts etc equipment with a strong magnetic field large diffusers etc in places subject to dir...

Page 11: ...it possible to upload and download the device settings and personalise the graphics recipes and languages using an ordinary USB flash drive see section 11 USB PORT MANAGEMENT The RS 485 MODBUS communi...

Page 12: ...to upload and download the device settings and personalise the graphics recipes and languages using an ordinary USB flash drive see section 11 USB PORT MANAGEMENT The RS 485 MODBUS communications port...

Page 13: ...ake sure that the supply voltage electrical frequency and power of the device correspond to the local power supply See section 1516 TECHNICAL SPECIFICATIONS Disconnect the device from the power supply...

Page 14: ...Operating modes The controller has the following operating modes OFF no power to the device STAND BY the device is powered but switched off ON HOME the device is powered switched on and awaiting start...

Page 15: ...e screen for longer than 10 minutes with no cycle running it will automatically go back to the stand by page 4 From the settings key on the stand by screen enter the GENERAL SETTINGS DATE TIME menu to...

Page 16: ...ill be automatically deactivated after the number of seconds set by parameter E1 unless it is silenced manually first 6 2 Home screen The Home screen is the departure point for navigating the user int...

Page 17: ...n Once a cycle has been started up the Run screen will appear for the type of cycle selected Below are the screens for the retarding proofing cycles E12 1 RETARDING PROOFING CYCLE HEATING CYCLE COOLIN...

Page 18: ...sor active flashing compressor start up delay in progress N B only present in the retarding proofing configuration On fans working flashing during an ON OFF cycle time OFF On defrosting in progress fl...

Page 19: ...tch light on off select fan speed if configured for several speeds enter additional functions exit additional functions start up selected cycle or recipe finish cycle in progress go from stand by to O...

Page 20: ...only When this option is pressed manual defrost starts up if the conditions are met 6 5 2 Sanitation The sanitation cycle can be carried out with a UV lamp or an ionizer ozone generator depending on p...

Page 21: ...me the compressor was switched off Compressor operation time can be reset in this screen and compressor maintenance time is reset accordingly 6 5 6 General settings This option gives access to the fol...

Page 22: ...access levels menu Every user who is logged in as ADMIN can set or change the user password and enable disable access to the various menu options Once the user configurations have been completed it is...

Page 23: ...of retarding proofing phases BLOCKING 5 10 C RH 4 6 hours HOLDING 2 2 C RH variable duration RE AWAKENING 10 13 C 70 80 RH 1 5 hours PROOFING 25 30 C 85 90 RH 2 4 hours BAKING DELAY 15 30 C 85 90 RH...

Page 24: ...se is calculated automatically by the controller on the basis of the duration of the blocking re awakening and proofing phases and the date and time for the end of proofing required for the dough Pres...

Page 25: ...t is set by the end user Moving from the re awakening setpoint previous phase to the proofing setpoint can be gradual with the incremental percentages set while the parameters are being set parameters...

Page 26: ...end user the cycle is automatically interrupted by holding down the STOP key This may be done when setting the cycle and with the cycle in progress Temperature regulation is active and has a neutral z...

Page 27: ...played Phases which have already been performed will have the message END instead of the duration The duration of the phases cannot be changed while the cycle is running Retarding proofing Proofing 7...

Page 28: ...started up from the default recipe or a pre existing recipe Press the automatic cycle area and view the recipes Upon selecting the desired recipe a table with a summary of the settings for every phas...

Page 29: ...ng holding re awakening proofing and baking delay or a PROOFING cycle re awakening proofing and baking delay Retarding proofing Proofing Press the arrows at the top of the display to move backwards an...

Page 30: ...e message CYCLE COMPLETED will appear if parameter E2 is configured The cycle can be interrupted manually during any phase by holding the STOP key down for a few seconds When managing retarding proofi...

Page 31: ...red in the table 2 overwrite a cycle recipe which has previously been selected and changed 3 save a new cycle recipe 4 view a cycle recipe in the favourites 5 delete customised values and go back to t...

Page 32: ...will be suggested the next time the cycle is selected Before starting up the desired cycle the values of the temperature setpoint humidity setpoint and fan speed can be changed if a timer is not set...

Page 33: ...de to these values they will be suggested the next time the cycle is selected The values of the temperature setpoint and fan speed can be changed before starting up the desired cycle if a timer is not...

Page 34: ...ng the START key When the cycle has been activated the controller automatically goes to the main page and displays the cabinet temperature and the setpoint to reach in the place of the pre cooling key...

Page 35: ...FAVOURITES In the RECIPE BOOK section users can save up to 99 cycles recipes only cycles recipes which have previously been labelled with the icon in the RECIPE BOOK can be stored in the FAVOURITES s...

Page 36: ...s are set one above and one below the temperature setpoint thus creating a zone inside which the loads for heating and cooling are not activated When the temperature rises above the neutral zone value...

Page 37: ...steam generator output and a humidifier output can be configured by parameter E4 If parameters E3 0 E4 0 E5 0 and E6 0 the steam generator output is always active The humidifier steam injection outpu...

Page 38: ...midity returns to within the dehumidification neutral zone value When managed by the refrigeration plant if the pump down solenoid valve is enabled parameter uxc 8 there will be a first attempt at deh...

Page 39: ...compressor is deactivated as follows and depends on the configuration of u2 and the configuration parameters of the multi purpose digital inputs if u2 is set to 0 deactivation of the compressor and t...

Page 40: ...the On Stand by screen or during a cycle in progress Depending on the value of parameter d1 the machine will perform either electric or hot gas defrost cycles or when the compressor stops If the evapo...

Page 41: ...naged 10 7 1 Humidifier output management without a probe or transducer This kind of management is obtained with the following settings rU0 1 and E3 0 The humidifier output will remain active for a du...

Page 42: ...m 10 9 Condenser fan management for retarding proofing only The condenser fan is managed by assigning a value of 3 to one of the relay outputs If the condenser probe is enabled see parameters Pr1 Pr2...

Page 43: ...on the cooling phase setpoint 2 Cooling adjustment phase During this phase probe connection is checked the temperature of the evaporator probe must be lower than that of the cabinet while the temperat...

Page 44: ...rnet connectivity which also enable alternative or parallel control through MODBUS TCP For more details compare the connectivity options in the Models available and technical features table and consul...

Page 45: ...troller with native EPoCA technology and connectivity which is either built in or provided by external hardware modules All devices are configured using the dedicated EPoCA Start mobile app The respon...

Page 46: ...in the USB flash drive upload to the controller the parameters in the USB flash drive upload to the controller CSV files to personalise the graphics recipes and languages Before inserting the flash dr...

Page 47: ...buzzer if enabled will begin to sound if several alarms are in progress at the same time they will alternate on the bar every 3 seconds When the alarm bar is pressed the buzzer will be silenced and th...

Page 48: ...as high pressure Main results the compressor and evaporator fan are switched off the condenser fan remains on LOW PRESSURE To correct check the state of the low pressure input check the value of the p...

Page 49: ...device probe connection check the cabinet temperature Main results if the error occurs during stand by it will not be possible to start up an operating cycle if the error happens during a cycle the cy...

Page 50: ...rect make sure the wiring is correct and intact check the inverter is powered correctly INVERTER SYNCHRONISATION To correct check there is communication between Vcolor and the inverter if the problem...

Page 51: ...bled 1 enabled P2 0 1 0 temperature measurement unit 0 C 1 F N B if this parameter is changed the device will automatically start up again P3 1 240 min 10 duration of power outage during a cycle due t...

Page 52: ...kening proofing baking delay and manual heating phases rH2 rH1 99 0 C 40 0 maximum possible setpoint for the re awakening proofing baking delay and manual heating phases rH3 0 0 10 0 C 1 0 value of he...

Page 53: ...proofing step out of a total of 100 Par Min Max Unit Default Humidity regulator rU0 0 1 0 humidity management mode 0 with humidity probe transducer only if P12 0 1 without humidity probe transducer t...

Page 54: ...ing proofing and baking delay phases C6 0 0 164 0 C 70 0 condensation temperature above which the condenser pre alarm overheat message is displayed C7 0 0 164 0 C 80 0 condensation temperature above w...

Page 55: ...drip time during dripping the compressor and evaporator fan will remain off and the defrost output will be deactivated d15 0 99 min 0 minimum consecutive compressor on duration for starting hot gas de...

Page 56: ...g the pre cooling phase F11 1 10 10 fan speed during the dehumidification phase F12 0 15 min 2 fan stop after the dripping phase F13 0 250 s 0 evaporator fan switch off delay from main load switch off...

Page 57: ...99 9 C 25 0 cabinet temperature setpoint in manual heating MH2 1 10 10 fan speed in manual heating MH3 0 100 80 humidity setpoint in manual heating MH4 0 5999 min 180 duration manual heating Par Min...

Page 58: ...ompressor is switched off 5 GENERIC ALARM displayed only 6 THERMAL SWITCH ALARM all loads are switched off 7 DEVICE SWITCH ON OFF 8 EVAPORATOR FAN THERMAL SWITCH ALARM humidifier steriliser oxygenator...

Page 59: ...u4 0 1 1 deactivation alarm output relay if buzzer silenced on keypad 0 no 1 yes u5 99 0 99 0 C 5 0 cabinet temperature under which the door frame heater is activated u6 0 1 1 enable alarm buzzer 0 n...

Page 60: ...uration cooling phase of testing cycle T8 1 20 2 number of compressor cycles cycle means ON time OFF time T9 99 0 99 0 C 2 0 RECOVERY PHASE CYCLE STOP setpoint Par Min Max Unit Default Serial communic...

Page 61: ...ed as 2 and 10 2 10 steps 0 10V output or EVCO inverter on 485 serial port 3 10 steps PWM output with EVC99E00X7XXX01 module or EVCO inverter on 485 serial port 4 as configuration E7 1 but with 2 rela...

Page 62: ...percentages set Check that the settings for the percentages and number of steps are consistent 2 The value set for parameter E7 only applies to Vcolor 679 models with PWM output make sure the paramet...

Page 63: ...e phase fan speed with a PWM command signal The maximum operating current is 5 A 15 3 EVCO Inverter Enables modulating management of asynchronous motors Compact series EI750M2C04O0VXX EI1K5M2C04O0VXX...

Page 64: ...tallation 0812000002 The plug makes the USB communications port of the device more accessible To connect the device to the plug connecting cable 0810500018 or 0810500020 must be used to be ordered sep...

Page 65: ...ng the EPoCA cloud system 15 10 IoT EV3 Web gateway EV3W01 IoT gateway with Ethernet connectivity and data logging functions to remotely monitor and control an RS 485 MODBUS RTU network with up to 10...

Page 66: ...x 4 566 x 1 732 in L x H x D Mounting methods for the control device user interface control module flush with the panel from behind with threaded studs not provided to hold it in place or semi recesse...

Page 67: ...tonomy in the absence of a power supply 6 months at 25 C 77 F Clock battery charging time 24 h the battery is charged by the power supply of the device Analogue inputs 5 inputs of which 3 for PTC NTC...

Page 68: ...le output 1 16 A res 250 VAC type SPST K6 configurable output 1 16 A res 250 VAC type SPST K7 configurable output 1 10 A res 250 VAC type SPST K8 configurable output 1 10 A res 250 VAC type SPST K9 co...

Page 69: ...VCO and thus protected by the Italian Intellectual Property Rights Code CPI EVCO forbids the reproduction and distribution even in part of the contents unless express authorisation is obtained directl...

Page 70: ...EVCO S p A Vcolor 679 689 Installer manual ver 1 0 Code 144VC679I104 page 70 of 70 EVCO S p A Via Feltre 81 32036 Sedico Belluno ITALY Tel 39 0437 8422 Fax 39 0437 83648 info evco it www evco it...

Reviews: