EVCO S.p.A.
Vcolor 679/689
| Installer manual ver. 1.0 | Code 144VC679I104
page 50 of 70
Main results:
-
none; this is only a visual alarm and has no effect on regulation
RTC
To correct:
-
re-set the date and time
Main results:
-
the device is unable to start up automatic cycles
-
any automatic cycles in progress will be blocked
NO BOARD COMMUNICATION
To correct:
-
check the user interface-control module connection
Main results:
-
cycle in progress interrupted
EXPANSION COMMUNICATION
To correct:
-
check the connection between the expansion and the control module
Main results:
-
cycle in progress interrupted
INVERTER COMMUNICATION
To correct:
-
make sure the wiring is correct and intact
-
check the inverter is powered correctly
INVERTER SYNCHRONISATION
To correct:
-
check there is communication between Vcolor and the inverter
-
if the problem persists when there is communication between Vcolor and the
inverter, contact EVCO’s technical support
INVERTER UNDERVOLTAGE
To correct:
-
check the characteristics of the motor
-
check the inverter is powered correctly
INVERTER OVERVOLTAGE
To correct:
-
check the characteristics of the motor
-
check the inverter is powered correctly
INVERTER OVERLOAD
To correct:
-
check the characteristics of the motor
-
check the wiring
INVERTER OVERCURRENT
To correct:
-
check the characteristics of the motor
-
check the wiring
INVERTER HEAT SINK OVERHEAT
To correct:
-
check the inverter is powered correctly
-
check the inverter is aired correctly