EVCO S.p.A.
EVDRIVE04 | User manual ver. 4.0 | Code 144EPDE404
page 72 of 78
Analog inputs:
4 inputs of which 2 inputs (non optoisolated, which can be set via
configuration parameter for NTC/Pt 1000 probes and for 0-20
mA/4-20 mA/0-5 V ratiometric transducers) which can be set via
configuration
parameter
for
suction
temperature
backup
probe/suction pressure backup probe, 1 input (non optoisolated,
which can be set via configuration parameter for NTC/Pt 1000
probes) as suction temperature probe and 1 input (non
optoisolated, which can be set via configuration parameter for
0-20 mA/4-20 mA/0-5 V ratiometric/0-10 V transducers) as suction
pressure probe.
NTC analog inputs (10K
Ω
@ 25 °C, 77 °F)
Kind of sensor:
ß3435.
Working range:
from -40 to 110 °C (from -40 to
230 °F) for standard NTC probes
from -50 to 150 °C (from -58 to
302 °F) for high temperature NTC
probes
from -50 to 110 °C (from -58 to
230 °F) for fast NTC probes.
Accuracy:
±0.6% of the full scale for standard
and fast NTC probes
±0.5% of the full scale for high
temperature NTC probes.
Resolution:
0.1 °C (1 °F).
Conversion time:
100 ms.
Protection:
none.
Pt 1000 analog inputs (1K
Ω
@ 0 °C, 32 °F)
Working range:
from -100 to 400 °C (from -148 to
752 °F).
Accuracy:
±0.5% of the full scale.
Resolution:
0.5 °C (1 °F).
Conversion time:
100 ms.
Protection:
none.
0-20 mA/4-20 mA analog inputs
Input resistance:
≤ to 200 Ω.
Accuracy:
±1% of the full scale.
Resolution:
0.01 mA.
Conversion time:
100 ms.
Protection:
none;
the
maximum
current
allowed on each input is 25 mA.