2 = from CAN bus
3 = reserved
4 = from serial Modbus RS-485
5 = from serial Modbus USB
6 = from CAN bus + DI1/2 in
communication error
7 = reserved
8 = from serial Modbus RS-485 +
DI1/2 in comm. error
9 = from serial Modbus USB + DI1/2
in comm. error
Pr08
1631
RW
0
255
s
5
Installer
Stabilization delay
Pr09
1632
RW
0.00
100.00
%
100.00
Installer
Stabilization position
Pr10
1638
RW
0.0
25.0
K
1.0
User
Dead band threshold
Pr11
1640
RW
Pr10
25.0
K
3.0
User
Smart band threshold
Pr12
1637
RW
1
100
-
70
User
Fast action level
Pr13
1642
RW
-10.0
10.0
K
-1.0
User
Fast action threshold
Pr14
1641
RW
0
255
100ms
10
User
SH filter time constant
Pr20
1604
RW
0.00
100.00
%
0.00
Installer
Stand by position
If Pr20 = 0% the valve closed to 0 steps
instead Minimum regulation step
Pr30
1605
RW
50.00
100.00
%
100.00
Manufact.
Limit valve opening
Pr40
1606
RO
0
9999
h
0
User
Working hour
Pr41
1607
RW
0
365
day
1
Installer
Resynchronization interval
0: disabled
Pr45
1608
RW
30
100
%
100
Manufact.
Valve duty cycle
Pr48
1609
RW
0.00
100.00
%
0.00
Installer
Communication error position
If Pr48 = 0% the valve closed to 0 steps
instead Minimum regulation step
Pr50
1610
RW
0
Pr51
step
200
Manufact.
Minimum regulation step
Pr51
1611
RW
Pr50
9999
step
1596
Manufact.
Maximum regulation steps
Pr52
1612
RW
Pr51
9999
step
1600
Manufact.
Overdrive steps
Pr53
1613
RW
25
1000
step/s
200
Manufact.
Stepping rate
Pr54
1614
RW
0
1000
mA
120
Manufact.
Operating phase current
Pr55
1615
RW
0
1000
mA
0
Manufact.
Holding phase current