EVCO S.p.A.
EVDRIVE04 | User manual ver. 1.0 | Code 144EPD4I104
Page 20 of 78
6.1.2
Valve selection
To select the desired valve, it is necessary to set the correct value in Valve selection (parameter Pi07).
Setting this parameter to a value of 0 (generic valve) means setting the parameters Pr50 to Pr55 is required, with
which it is possible to specify the value of each valve parameter.
With function “Copy selected to generic valve” it is possible to copy the default values of the selected valve into the
ones of the generic valve, in order to use them as reference for possible modifications.
If a predefined valve is selected (parameter Pi07 > 0), all relevant parameters specific to that valve are loaded
automatically from the flash memory, according to the table below:
P
i0
7
V
a
lv
e
n
a
m
e
M
in
im
u
m
r
e
g
u
la
ti
o
n
s
te
p
s
[
s
te
p
]
M
a
x
im
u
m
re
g
u
la
ti
o
n
s
te
p
s
[
s
te
p
]
O
v
e
rd
ri
v
in
g
s
te
p
s
[
s
te
p
]
S
te
p
p
in
g
ra
te
[
s
te
p
/s
]
O
p
e
ra
ti
n
g
p
h
a
s
e
c
u
rr
e
n
t
[m
A
]
H
o
ld
in
g
p
h
a
s
e
c
u
rr
e
n
t
[m
A
]
R
e
c
o
m
m
e
n
d
e
d
S
te
p
M
o
d
e
0
Generic valve
0
0
0
0
0
0
Full step 2ph
1
Sporlan CO2
0
2500
3125
400
275
0
Full step 2ph
2
Sporlan SER AA
Sporlan SER A
Sporlan SER B
Sporlan SER C
Sporlan SER D
0
2500
3500
400
120
0
Full step 2ph
3
Sporlan SERI F
Sporlan SERI G
Sporlan SERI J
Sporlan SERI K
Sporlan SERI L
0
2500
3500
400
120
0
Full step 2ph
4
Sporlan SER 1.5 to 20
0
1596
3500
400
160
0
Full step 2ph
5
Sporlan SEI 0.5 to11
0
1596
3500
400
160
0
Full step 2ph
6
Sporlan SEI 30
0
3193
6500
400
160
0
Full step 2ph
7
Sporlan SEI 50
0
6386
7500
400
160
0
Full step 2ph
8
Sporlan SEH 100
0
6386
7500
400
160
0
Full step 2ph
9
Sporlan SEHI 175
Sporlan SEHI 400
0
6386
6500
400
160
0
Full step 2ph
10
Sporlan SDR-3
0
3193
3512
200
160
0
Full step 2ph
11
Sporlan SDR-4
0
6386
7025
200
160
0
Full step 2ph
12
Sporlan ESX unipolar
24
224
300
40
260
0
Full step 2ph
13
Sporlan EDEV B unipolar
Sporlan EDEV C unipolar
0
800
1250
200
120
0
Half step
20
Castel 261
0
415
515
35
200
0
Full step 2ph
21
Castel 262
Castel 263
0
195
255
25
200
50
Full step 2ph
22
Castel 264
0
985
1135
70
560
50
Full step 2ph
30
Alco EXM unipolar
Alco EXL unipolar
16
250
350
45
130
0
Half step
31
Alco EX4
Alco EX5
Alco EX6
0
750
1000
500
500
100
Full step 2ph
32
Alco EX7
0
1600
2000
500
750
250
Full step 2ph
33
Alco EX8
0
2600
3250
500
800
500
Full step 2ph
40
Danfoss ETS 12C
Danfoss ETS 24C
Danfoss ETS 25C
Danfoss ETS 50C
Danfoss ETS 100C
0
600
628
240
800
0
Full step 2ph
41
Danfoss ETS 12.5
Danfoss ETS 25
Danfoss ETS 50
0
2625
3150
300
100
75
Full step 2ph
42
Danfoss ETS 100
0
3530
4250
300
100
75
Full step 2ph
43
Danfoss ETS 250
Danfoss ETS 400
0
3810
4550
300
100
75
Full step 2ph
44
Danfoss ETS 6 unipolar
0
240
260
25
260
0
Half step
50
Sanhua VPF 12.5
Sanhua VPF 25
Sanhua VPF 50
0
2600
3000
300
140
0
Full step 2ph
51
Sanhua VPF 100
0
3500
4400
300
140
0
Full step 2ph
52
Sanhua VPF 150
Sanhua VPF 250
Sanhua VPF 400
0
3800
4400
300
140
0
Full step 2ph
The driving mode can be selected through parameter Driving mode selection (Pi01). If value 0 is selected (Pi01=0) the
driving mode is automatically calculated to ensure the maximum speed according to the step rate of the selected valve.