EVCO S.p.A.
EVDRIVE04 | User manual ver. 1.0 | Code 144EPD4I104
Page 53 of 78
UdM
1645
RO
- - - -
- - - -
- - - -
- - - -
User
internal unit of measure
b0:
0: pressure in bar
1: pressure in psi
b1:
0: temperature in °C/K
1: temperature in °F/R
b2:
0: conversion ok
1: conversion in progress or
halted
DrvM
1792
RO
0
5
- - - -
- - - -
User
driving mode
0 = full step 2 ph on
1 = full step 1 ph on
2 = half step
3 = microstepping 4
4 = microstepping 8
5 = microstepping 16
Stat
1793
RO
0
61
- - - -
- - - -
User
FSM status
0 = initialization
1 = synchronization wait
2 = positioning wait
3 = probe alarm
4 = grid alarm
5 = communication alarm
10 = stand-by off
11 = stand-by on
30 = analog positioner
40 = stabilization
41 = start-up
42 = algorithm selection
50 = manual
51 = debugger
60 = reserved
61 = SH algorithm
AlSt
1794
RO
- - - -
- - - -
- - - -
- - - -
User
alarm status
b0:
EEPROM alarm
b1:
configuration alarm
b2-3: communication status
b4-7: probe alarm
b8:
power fail
b9:
backup battery alarm
b10: algorithm alarm
b11: reserved
b12: parameters conversion failed
AlgS
1795
RO
- - - -
- - - -
- - - -
- - - -
User
SH algorithm status
b0:
measure not acquired
b1:
algorithm halted
b2:
bypass algorithm (manual)