EVCO S.p.A.
EVDRIVE04 | User manual ver. 1.0 | Code 144EPD4I104
Page 52 of 78
Ps05
1706
RW
-
32768
32767
-
0
User
Probe 1 Simulation value
tenths of a degree if configured as a
temperature probe
hundredths of mA if configured as a
current probe
Ps06
1706
RW
-
32768
32767
-
0
User
Probe 2 Simulation value
tenths of a degree if configured as a
temperature probe
hundredths of mA if configured as a
current probe
Ps07
1706
RW
-
32768
32767
-
0
User
Probe 3 Simulation value
tenths of a degree if configured as a
temperature probe
hundredths of mA if configured as a
current probe
Ps08
1706
RW
-
32768
32767
-
0
User
Probe 4 Simulation value
hundredths of mA if configured as a
current probe
hundredths of V if configured as a
voltage probe
Par.
Add. Acc.
Min.
Mas.
Unità
Default
Menù
Comandi
Pr02
1596
RW
0
2
-
0
Utente
Functioning mode
0: SH-algorithm
1: manual mode
2: debug functionality
Pr03
1597
RW
0.00
100.00
%
0.00
Utente
Manual set-point position
used if valve in manual mode (Pr02=1)
ResR
1281
RW
0
1
-
0
Utente
Resynch request
0
→
1 resynch request
EnaV
1282
1285
RW
0
1
-
0
Utente
Enable valve command
1282: Modbus RS-485
1285: Modbus USB
0 = disable valve
1 = enable valve
Cmd
1286
RW
0
65535
-
0
Utente
Command
b0: 0
→
1 reset parameter alarm
Cmd: x
→
0xBx reset application (Init
phase)
Cmd: x
→
0x5x reset board
Cpy
1812
WO
0
255
-
0
Utente
Copy selected to generic valve
1 to Pi07 max: copy the selected valve
parameters to generic valve parameter
Par.
Add. Acc.
Min.
Mas.
Unità
Default
Menu
Status