EVCO S.p.A.
EVDRIVE04 | User manual ver. 1.0 | Code 144EPD4I104
Page 46 of 78
8 = Sporlan SEH 100
9 = Sporlan SEHI 175/400
10 = Sporlan SDR-3
11 = Sporlan SDR-4
12 = Sporlan ESX UNI
13 = Sporlan EDEV B/C UNI
20 = Castel 261
21 = Castel 262/263
22 = Castel 264
30 = Alco EXM/L UNI
31 = Alco EX4-6
32 = Alco EX7
33 = Alco EX8
40 = Danfoss ETS 12-100C
41 = Danfoss ETS 12.5-50
42 = Danfoss ETS 100
43 = Danfoss ETS 250/400
44 = Danfoss ETS 6 UNI
50 = Sanhua VPF 12.5-50
51 = Sanhua VPF 100
52 = Sanhua VPF 150-400
Par.
Add. Acc.
Min.
Mas.
Unità
Default
Menu
Valve
and
driver:
digital
I/O
settings and various
Ph01
1620
RW
0
8
- - - -
0
Manufact.
digital output DO1 function
0 = disabled
1 = any alarm
2 = probe errors
3 = following low SH alarms
4 = following MOP alarms
5 = following valve alarm
6 = used for solenoid valve
7 = alarms + used for solenoid
valve
8 = valve resyncchronization signal is
necessary
Ph02
1621
RW
0
1
- - - -
0
Manufact.
relay logic
0 = normally unexcited
1 = normally excited
Ph10
1622
RW
0
1
- - - -
0
Manufact.
free of voltage digital input DI1 logic
0 = normally open
1 = normally closed
Ph11
1623
RW
0
4
- - - -
1
Manufact.
free of voltage digital input DI1 function
0 = none
1 = enable/disable valve
2 = change parameters set
3 = resynchronization request