7.3
Configuring a blind version
The following procedures show an example of configuration of a blind version through an user interface (in the
example EPJgraph) and through its user interface.
For further information please consult the hardware manual of the user interface.
Operate as follows:
1.
Switch off the power supply of the device and of the interface.
2.
Connect the device to the interface through the CAN port; look at chapter 4 “ELECTRICAL CONNECTION”.
3.
Keep pressed 2 s buttons ESC and RIGHT.
4.
Switch on the power supply of the device and of the interface.
5.
When the display of the interface will show the following menu release buttons ESC and RIGHT.
EPJgraph
Parameters
Contrast
CAN Network
Modbus
Info
Real date and time
6.
Press and release button UP or button DOWN to select “
CAN Network
”.
7.
Press and release button ENTER.
8.
Press and release button ENTER again to set the password value.
9.
Press and release button DOWN over and over again to set “
-19
”.
10.
Press and release button ENTER again.
11.
Set parameter
NW Node
using button UP or button DOWN to select the parameter and using button ENTER to
modify and to confirm the value.
According to the factory setting the address of the CAN node of an electronic expansion valve driver has value
11
(therefore operate on the interface to set parameter
NW Node
to
[ 1 ] 11
).
12.
Switch off the power supply of the interface.
13.
Switch on the power supply of the interface.
14.
Keep pressed 2 s buttons LEFT and ENTER: the display will show the following menu.
Network Status
Loc
99
OK
> >
1
11
OK
> >
2
0
-
> >
3
0
-
> >
4
0
-
> >
5
0
-
> >
15.
Press and release button UP or button DOWN to select the device.
16.
Press and release button ENTER: the display will show page 1 of the device.
17.
Operate as shown in paragraph 7.2 “Configuring a built-in version”.