Chapter 3 WIRING
WIRING - SAFETY
TE200 series units have an IP20 protective cover.
Danger !
Wiring must only be carried out by personnel who are qualified to work in a low
voltage industrial environment.
It is the user’s responsibility to wire and protect the installation in accordance with
current professional Standards. A suitable device ensuring electrical isolation
between the equipment and the supply must be installed upstream of the unit in
order to permit safe operation.
Danger !
Before any connection or disconnection, ensure that power and control cables or
leads are isolated from voltage sources.
For safety reasons, the safety earthing cable must be connected before any other
connection is made during wiring and it should be the last cable to be
disconnected. The safety earth is connected to the screw located on the upper part
of the controller and is denoted by the symbol:
Warning !
To ensure correct grounding (EMC) of the TE200S unit, make sure that it is
correctly mounted on the reference ground surface (panel or bulkhead).
Failing this, it is necessary to add a ground connection at most 10cms long
between the earth connection and the reference ground surface.
Danger !
This connection, which is intended to ensure good ground continuity, can never be
used to replace the safety earth connection.
WIRING
!