TE200S User manual
1-6
IDENTIFYING THE SOLID STATE RELAYS
Thyristor firing
Firing mode
Logic ON/OFF
Switching
Firing starts and ends at zero voltage
Indication
Thyristor firing is signalled by a green LED
Control
Signal type
DC Logic or AC Logic
The signal type (DC or AC) is configured at the factory
according to the order code; it cannot be re-configured by
the user
DC signal
Universal input: voltage or current.
Polarity insensitive: ‘+’ and ‘-’ can be crossed
‘On’ state
Guaranteed conditions for firing:
voltage greater than 5Vdc or
current greater than 5mA
Maximum voltage: 32Vdc.
Maximum current (self-limited) 10mA at 32Vdc
‘Off’ state
Voltage less than 2Vdc or current less than 0.5mA
AC signal 24 to 48 Vac
Typical input impedance 2.2k
Ω
(50Hz & 60Hz)
‘On’ state
Guaranteed conditions for firing:
voltage from 20Vac to 53Vac
‘Off’ state
Voltage less than 5Vac
AC signal 100 to 230 Vac
Typical input impedance 9.6k
Ω
(50Hz); 8.0k
Ω
(60Hz)
‘On’ state
Guaranteed conditions for firing:
voltage from 85Vac to 253Vac
‘Off’ state
Voltage less than 10Vac
Environment
Operating temperature
0°C to +60°C at maximum altitude of 2000m (see page
1-2 for derating curves)
Storage temperature
-10°C to +70°C
Thyristor protection
External high-speed fuses except for short-wave infrared
application (see chapter 5)
Internal MOVs (varistors) and RC snubbers
Protection
IP20 (in compliance with Standard IEC 529)
External wiring
To be carried out in compliance with Standard IEC 364
Operating atmosphere
Non-explosive, non-corrosive, non-conductive
Humidity
RH: 5% to 95%, non-condensing, non-streaming
Pollution
Pollution degree 2 permissible, defined by IEC 664
Over-voltage category III, defined by IEC 664
Summary of Contents for TE200S