TE200S User manual
4-4
Fan supply voltage (63A rated unit)
For 63A rated fan-cooled SSRs, the fan must be provided with a 115Vac or 230Vac supply.
The fan supply voltage is set at the factory, depending on the product code ordered.
Control signals
Configuration of the input type required by the user is also set at the factory, depending on the
product code ordered.
Check that the label on the front facia corresponds to the control setup:
Terminals 8 and 9
• No legend - DC logic input
• “AC Input” legend:- 24 to 48Vac input
• “HAC Input” legend:- 100 to 230Vac input
POWERING UP
TE200S series SSRs are ready to operate correctly immediately after installation and wiring in
accordance with this user manual.
After checking that the nominal parameters of the SSR (voltage, current, input signal) are
compatible with those of the installation, apply volts to the SSR.
Check that the current in each phase of the SSR is equal to 0 in the absence of the control
signal.
Make sure that the r.m.s. current in each phase does not exceed the nominal rating when the
control signal is present.
COMMISIONING PROCEDURE