Part N
°
: HA176063 ENG - issue 1.2 - 05/01
ADDENDUM
to User Manuals
TE200S
Part N
°
HA175921 ENG
TE200A
Part N
°
HA175773 ENG
MAXIMUM CURRENT
and
SHORT WAVE INFRARED APPLICATIONS
• MAXIMUM CURRENT
In order to take into account supply voltage variations and heating element
resistance dispersion (all types of heating elements including short wave infrared),
a 0.8 safety coefficient must be used on the thyristor unit current rating to determine
the maximum value of the load nominal current which the unit can safely control.
• SHORT WAVE INFRARED (SWIR) APPLICATIONS
Applications using short wave infrared heaters in Single Cycle, Fast Cycle or
Advanced Single Cycle are reserved to 16 A, 25 A and 40 A current rating.
With a safety coefficient of 0.8 the maximum current for SWIR which can be
controlled is:
© Copyright Eurotherm Automation S.A. 1998
All rights strictly reserved. No part of this document
may be stored in a retrieval system, or any form or by
any means without prior written permission from
Eurotherm Automation SA.
Current rating
SWIR maximum
controlled current
16 A
230 V and 400 V : 13 A
25 A
230 V : 16 A, 400 V : 13 A
With Special 601
230 V and 400 V : 20 A
40 A, 50 A and 63 A
230 V : 28 A, 400 V : 25 A