INSTALLATION
Chapter 2 INSTALLATION
Please read thoroughly before installing the SSR
INSTALLATION - SAFETY
Danger !
TE200S units must be installed by personnel qualified and trained to work with
low voltage electrical equipment in an industrial environment.
Units must be installed in electrical cabinets correctly fan-cooled to ensure that
condensation and pollution are excluded.
The cabinet must be closed and bonded to the safety earth in accordance with
Standards NFC 15-100, IEC 364 or current national Standards.
For installations which are fan-cooled, it is recommended that a fan-failure detection device
or a thermal safety cut-out should be fitted in the cabinet.
TE200S units may be bulkhead or DIN rail mounted.
The units must be mounted with the heatsink positioned vertically, with no obstructions
above or below which could inhibit or impede airflow.
If several units are mounted in the same cabinet, they should be arranged in such a way that
air expelled from one cannot be drawn into the unit located above it.
Warning !
The units are designed to be used at an ambient temperature less than or equal to
45°C at full load or up to 60°C at partial load (see Current derating curves, page
1-2).
Leave a minimum gap of 5cm between two units placed side by side.
Excessive overheating of the SSR may lead to incorrect operation of the unit. This
may in turn cause damage to the components.
!