6 . 3 LIST OF POSSIBLE ERRORS
LIST OF POSSIBLE ERRORS
LIST OF POSSIBLE ERRORS
LIST OF POSSIBLE ERRORS
LIST OF POSSIBLE ERRORS
100
EEPROM writing error.
Consult your supplier.
2xx
Error in the configuration parameters.
The two less significant figures indicate
the number of the incorrect parameter
(e.g.
209 Err
indicates error of
parameter P9).
Press and , then set the
parameter correctly.
See section 4.
301
RTD input calibration error.
Contact your supplier.
305
TC input calibration error.
Contact your supplier.
307
RJ input calibration error.
Contact your supplier.
400
Error in the operative parameters.
Error in the operative parameters.
Error in the operative parameters.
Error in the operative parameters.
Error in the operative parameters.
To deal with the problem, enter
To deal with the problem, enter
To deal with the problem, enter
To deal with the problem, enter
To deal with the problem, enter
the predefined parameters
the predefined parameters
the predefined parameters
the predefined parameters
the predefined parameters
(“Default Parameters”, see
(“Default Parameters”, see
(“Default Parameters”, see
(“Default Parameters”, see
(“Default Parameters”, see
section B), pressing pushbuttons
section B), pressing pushbuttons
section B), pressing pushbuttons
section B), pressing pushbuttons
section B), pressing pushbuttons
and
and
and
and
and at the same time.
at the same time.
at the same time.
at the same time.
at the same time.
Then set the operative
Then set the operative
Then set the operative
Then set the operative
Then set the operative
p a r a m e t e r s .
p a r a m e t e r s .
p a r a m e t e r s .
p a r a m e t e r s .
p a r a m e t e r s .
500
Auto-zero error
Contact your supplier.
502
RJ error
Contact your supplier.
- The instrument is set to use two control outs
and an UNDERRANGE is detected, OUT 1 turns
ON and OUT 2 turns OFF.
For inputs from thermocouple the underrange
indication can be selected as shown in section 7.2
of this manual.
NOTE:
NOTE:
NOTE:
NOTE:
NOTE: When an
overrange
or an
underrange
is
detected, the alarms operate as if the
instrument had detected the maximum or
the minimum measurable value
respectively.
To eliminate the out of span condition, proceed as
follows:
1) Check the input signal source and the
connecting line.
2) Make sure that the input signal is in
accordance with the instrument configuration.
Otherwise, modify the input configuration (see
section 4).
3) If no error is detected, send the instrument to
your supplier to be checked.
6 . 2
6 . 2
6 . 2
6 . 2
6 . 2 ERROR MESSAGES
ERROR MESSAGES
ERROR MESSAGES
ERROR MESSAGES
ERROR MESSAGES
Diagnostics are made on switching on and during
normal operation.
If the instrument detects an error condition the
display will show:
0316:
“
Err
” in the lower display and the code
which identifies the type of error in the
upper display.
0216:
“
E
” and the error code.
The complete list of all the possible errors follows
in numerical order.
Some errors automatically reset the instrument: if
the error persists, send the instrument to your
supplier to be checked.