17
possible cause
• Closing limit switch
ACTIVATED
• Photocell test
• Motor test
• Power supply disconnected
• Permanent
START
command
•
STOP
button disconnected.
• Incorrect wiring.
• Photocell in
closing
non-aligned.
• Obstacle detected between the
photocel.
• Incorrect electric wiring.
• Disconnected photocell.
• Disconnected photocell
active input.
• Disconnected safety edge.
• Photocell in
opening
non-aligned.
• Obstacle detected between the
photocel.
• Incorrect electric wiring.
• Disconnected photocell.
• Permanent
PEDESTRIAN
command.
• Opening limit switch
ACTIVATED.
• Incorrect electric wiring.
• Bordo sensibile non collegato.
• Faulty safety edge.
Solution
Release and open the gate manually, the LED must turn on.
Check the wiring and operation of the photocell.
Check the wiring and operation of the motors.
Check the connection to the power supply (230V).
Check the operation of the ACCESSORIES wired to the
START
(N.O. contact, see section
3.3
).
Check the wiring otherwise deactivate the input.
Check the wiring diagram (see section
3.5
)
Check the photocell alignment.
Check and remove the obstacle.
Check the wiring diagram.
Check the power connection.
Disable the photocell input (see section
3.6
)
Check the connection (N.C.) and the good operation of the
safety edge.
Check the photocell alignment.
Check and remove the obstacle.
Check the wiring diagram.
Check the power connection.
Check the operation of the ACCESSORIES wired to the
PEDESTRIAN START
(N.O. contact).
Release and close the gate manually, the LED must turn on.
Check the wiring diagram and the good operation of the
micro switch in opening.
Check the wiring.
Check the safety edge conditions.
Led Error
DL9
OFF
DL1
2 blinks, stop,
2 blinks ....
3 blinks, stop
3 blinks ....
OFF
DL4
ON
DL5
OFF
DL7
OFF
DL8
OFF
DL6
ON
DL10
OFF
DL3
OFF
9. TROUBLE SHOOTING – ERROR MESSAGES
The control panel is designed to display errors through a LED lighting system.
Here below the trouble shooting table.