Euroalpi Pasubio Use And Maintenance Manual Download Page 14

14 

 

The pellet 

 
To obtain the maximum performance, the ZF company suggests to use pellets of the quality prescribed by 
the regulations DIN51731. 

 

Length: 30mm 
Diameter: 6mm 
Calorific value: 4.9 ÷ 5.3 kWh / kg 
Humidity max: 6% 

 

The  pellets  must  be  stored  in  a  dry  place  away  from  heat  sources.  The  ZF  company  assumes  no 
responsibility for malfunction due to the use of poor quality pellets. 

 

9 First ignition 

 

Warning 

The first ignition will have to be carried out by a qualified technician who will have to check: 

 

-

 

That all the regulations mentioned above and the current regulations in the place of installation 
have been applied. 

 

-

 

The correct installation: of the stove, the flue, the chimney pot. 

 

-

 

That there is no risk of damage to the stove or to the room of installation. In case of problems, the 
ZF company assumes no liability both civil and criminal. 

 

First steps 

Check that there are no objects on the stove (manual included) and proceed as follows: 

 

-

 

Fill  the  hopper  with  pellets,  opening  the  upper  door  and  closing  it  again,  making  sure  that  no 
foreign body is in the hopper. Take off the cover of the hopper only during its charging. 

 

-

 

Check that the brazier is well positioned in its place. 

 

 

-

 

Check that the door is hermetically closed. 

 

-

 

Supply power, put the general switch ON (it is placed in the back down side); the control display 
will light up. 

 

-

 

During the first few times, there may be cases of unpleasant smells due to the presence of greases 
and  oils  on  the  components  used  during  the  production  phase.  Ventilate  the  space  and  avoid 
staying there for long periods until the smells disappear. 

 

 

9.1 User interface 

 

The console unity permits to talk to the controller by simply pressing some buttons. A display and other 
LED  indicators  inform  the  operator  that  the  stove  is  working.  In  programming  mode  are  displayed  the 
different parameters that can be modified by pressing some buttons.

 

 
 

Summary of Contents for Pasubio

Page 1: ...Use and maintenance manual for pellet stove...

Page 2: ...ve and safety All the operations not considered in the manual and not authorized by a technician recommended by the company must be considered dangerous Otherwise the ZF company does not assume any re...

Page 3: ...maintenance not in compliance with the provisions in this booklet of Use and Maintenance can cause damage to people and things In this case the company ZF is released from any civil or criminal respon...

Page 4: ...5014 1 EN 55014 2 EN 61000 3 2 EN 61000 3 3 EN 60335 1 EN 60335 2 102 EN 62233 EN 50581 EN 14785 For the installation and the use of the stove all the local and national and all European standards mus...

Page 5: ...ses The above warranty terms have not been observed The installation is not carried out in full obedience of the laws in force and the instructions contained in the provided manual Non maintenance or...

Page 6: ...rom the warranty and they are Gaskets Ceramic tempered glass Upholstery and grills Varnished details Chromate gilded Satinized Majolica Handles Electric cables Vermiculite Refractory material Brazier...

Page 7: ...tion errors Non compliance with safety regulations Installation by unqualified and untrained personnel Installation not in accordance with the regulations in force in the country Use of non original s...

Page 8: ...it is compulsory the presence of a suitable fumes evacuation system It is not compulsory to connect the air intake tube of the stove directly outside see picture but it is recommended for a better eff...

Page 9: ...junction with inspection it is advisable to use curves of 45 Using nets or filters at the extremity of the flue or any extremity which could turn into a nest is forbidden Use only extremity in accord...

Page 10: ...is a fireplace it must have a preferably circular internal section the square or rectangular sections must have rounded corners with a radius of at least 20mm the rectangular sections with a maximum r...

Page 11: ...is assured windproof chimney pot The chimney pot must be positioned to guarantee an adequate dispersion and dilution of the combustion products and however outside the reflux area This area has differ...

Page 12: ...re and consequently in the opposite situation increases the depression decreasing the draught To overcome these drawbacks the installer must act directly on the stove modifying the parameter to adjust...

Page 13: ...eed reduced power 4 7 g s Min and Max draft 10 Pa 12 Pa Pellets tank capacity 17 Kg Pellet consumption at rated power 1 4 Kg h Pellet consumption at reduced power 0 7 Kg h Pellets autonomy at rated po...

Page 14: ...minal First steps Check that there are no objects on the stove manual included and proceed as follows Fill the hopper with pellets opening the upper door and closing it again making sure that no forei...

Page 15: ...the next submenu level PROGRAMMING It sets the selected value and passes to the next entry 4 ON OFF WORK Pressed for 2 seconds it turns on and off the stove PROGRAMMING It passes to the next level of...

Page 16: ...aller must carry out any other try he deems necessary and verify the operation of the buttons on the console 10 1 Igniting the stove Once the installation of the stove and the compulsory verification...

Page 17: ...1 minute the pellet loading phase begins the message LOAD PELLET passes on the display In a first phase the auger provides to load the pellets in the brazier for a time given by the parameter PR40 aug...

Page 18: ...PR13 and maintained it for at least a time PR02 the stove goes into working mode which is the normal operating The display will show the word WORK The power can be set by holding down the button P5 a...

Page 19: ...s acting on the buttons P1 increase and P2 decrease it is possible to change the value After about 5 seconds the value is saved and the display returns to the normal mode or press P3 to exit Figure 8...

Page 20: ...this state the stove has turned off the auger auger LED off the exchanger switches off when it reaches the threshold given by the parameter PR15 and the LED ON OFF flashes Figure 10a Figure 10a When t...

Page 21: ...e threshold given by the parameter PR10 the stove turns off displaying the message OFF Figure 11a Figure 11a 11 THE MENU You can enter the menu by pressing the P3 button The menu is subdivided into di...

Page 22: ...uesday Prg 2 on off 15 Wednesday Prg 2 on off 16 Thursday Prg 2 on off 17 Friday Prg 2 on off 18 Saturday Prg 2 on off 19 Sunday Prg 2 on off 20 start Prg 3 OFF 0 23 50 21 stop Prg 3 OFF 0 23 50 22 Mo...

Page 23: ...info 04 Fumes state info 05 Fumes extraction revolutions state info Level 1 Level 2 Value M8 technician settings 01 access key set Level 1 Level 2 Value M9 exit 01 exit set 11 2 Menu M1 SET CLOCK It...

Page 24: ...c the day figure 12d the month figure 12e and the year figure 12f by pressing the P1 button increment and P2 button decrement and confirming by pressing the P3 button Figure 12b Figure 12c Figure 12d...

Page 25: ...13a You can set two sections of functioning the first one with START1 Day and STOP1 Day and the second one with START2 Day and STOP2 Day delimitated by the times set according to the following table w...

Page 26: ...f M2 3 05 TUESDAY PRG 1 on off M2 3 06 WEDNESDAY PRG 1 on off M2 3 07 THURSDAY PRG 1 on off M2 3 08 FRIDAY PRG 1 on off M2 3 09 SATURDAY PRG 1 on off M2 3 10 SUNDAY PRG 1 on off PROGRAM 2 Menu level S...

Page 27: ...e functioning of the stove for Sunday by setting Start2 weekend and Stop2 weekend WEEKEND PROGRAM Menu level Selection Meaning Possible values M2 4 01 WEEKEND TIME Enable weekend time ON OFF M2 4 02 S...

Page 28: ...st ignition of the stove figure 17 when the pellet tank is empty After having selected the menu M6 the message P1 to load will pass on the display figure 17a Then press P1 increment The smokes fan tur...

Page 29: ...zed Meaning 3 1 Auger pellet load state 52 Time out Toff Thermostat state 106 Fumes temperature 1490 Fumes extraction speed Figure 18 11 9 Menu M8 Technician settings This menu entry is for the techni...

Page 30: ...the stove is initiated for safety During the alarm phase the alarms LED will always be on Alarm LED on and when enabled the buzzer it will sound intermittently If you don t reset the alarm the stove...

Page 31: ...extractor is not detected by the board In this case reset the alarm by pressing the On Off button and contact an authorized service center Figure 23 12 5 Firing failure alarm It occurs when the igniti...

Page 32: ...n put the cap back restart the stove and check if the environment fan is working correctly If the alarm persists call the Authorized Service Provider Figure 27 12 8 Alarm absence depression It occurs...

Page 33: ...flame did not bring the fumes on right temperature within the preset time The pellet is finished reload the tank turn the stove on if the problem persists call the authorized service The draught is n...

Page 34: ...hen the ash reaches the edge of the same drawer it is strictly forbidden to light the stove if the ash goes beyond it Every day when you clean the brazier also check if the drawer has to be emptied Th...

Page 35: ...d to the inner sides of the stove Remove the brazier to proceed with the removal of interior sides Remove the internal combustion chamber surround taking it by the two lower edges if this operation is...

Page 36: ...behind the support of the brazier there is another combustion chamber surround to remove it grab it by the edge and pull up Removed this part the two rear combustion chamber surrounds are released to...

Page 37: ...ning and physical state Do not reassemble broken or damaged parts that may cause the malfunction of the stove Summary scheme of the cleaning and maintenance of the stove Daily Every 3 days Every 15 da...

Page 38: ...al arising from the use of non original spare parts also informs that the use of these implicates the fall of the warranty on the stove You will find the complete list of spare parts and related code...

Page 39: ...corto inferiore 1 35 R2600424 Ferma vetro laterale sx 1 36 R2600425 Tappo inferiore 1 37 R2600427 Staffa supporto serbatoio coclea 1 38 R2600428 Staffa supp motore coclea 1 39 R2600430 Braciere 6 9 k...

Page 40: ...Below the diagram for the connection between the different electric parts and the motherboard of the stove is represented TSP safety thermostat pellet tank 15 Wiring diagram...

Page 41: ...The adjustment of the channeling can happen in two ways depending on the type of stove you have Manual Adjustment Automatic Adjustment Automatic Adjustment To adjust the fan press button 3 to go to t...

Page 42: ...Below there is an example of installation of ducted stove in a home...

Page 43: ...17 Notes...

Page 44: ...44 Notes...

Page 45: ...al waste but it must be assigned to specialized collection structures as prescribed by local regulations or by the dealer The importer and the dealer are responsible for collection and disposal both i...

Reviews: