13) Parameter group 600: DC-Brake control / aux. functions
13) Parameter group 600: DC-Bake control / Aux. functions
DC-Brake function parameters:
F600
DC-Brake function
activation
Selection: 0: DC-Brake deactivated
1: DC injection before START
2: DC injection after STOP
3: Before START and after STOP
Default setting 0
F601
Frequency threshold for
DC-injection
Range: 0.2…5.0 Hz
Default setting 1.00 Hz
F602
Intensity DC-Brake START
Range: 0…100%
Default setting 10
F603
Intensity DC-Brake STOP
F604
DC-Brake duration START
Range: 0.0 - 30.0 sec.
Default setting 0.5 sec.
F605
DC-Brake duration STOP
DC Brake can be used as an alternative to ramp controlled STOP
(F209=2).
Intensity is controlled by
(F603),
duration by
(F605)
.
Attention!! Improperly programmed DC-Brake function may result in inverter overcurrent
trip and/or motor overheating
In case of braking by DC injection all kinetic energy will be dissipated in the motor rotor.
Repeatedly use of the DC brake function may result in motor overheating
Message "DC-Brake active" may be configured through digital output – assignation code
6
Current- Voltage limiting functions
Limiting functions for current and voltage are available in standard E2000 inverters
Current limiting function: To program a motor current threshold. If motor current reaches the threshold (F608) during
acceleration, the acceleration ramp will delay, until current drops below the limit.
If current exceed the limit at target frequency (ramp completed), the frequency will be reduced, if necessary, down to
the minimum frequency.
Current limiting function is always deactivated during deceleration ramp.
Voltage limiting function: To limit the DC-link voltage increase, due to energy regeneration during deceleration phase.
If voltage reaches the limit (F609), the limiting function will stretch the deceleration ramp.
The limiting status of the inverter can be signalized through any programmable digital output. Aassignation code:
12
F607
Activation limiting functions
Selection: 0 deactivated
1..2: reserved
3: current/voltage
4: voltage
5: current
Default setting: 3
F608
Current limit (% rated current)
Range: 60…200 %
Default setting: 160 %
F609
DC voltage limit (% rated voltage)
Range: 60…200 %
Default setting: 140 %
F610
Max. duration if limiting status (sec.)
Bereich: 0.1…3000.0 sec.
Default setting: 5.0 sec.
If limiting status of the inverter takes longer than time, set in
F610
, the system will stop, signalized by
OL1
on the
display
t
V
/
A
F604
Hz
F
605
t
F601
F602
EM30 – Rev.03 -EN- SOFT Rev. 1.1x
© 2017-06-KPP-EURADRIVES EUROPE GmbH
49