11) Parameter group 400: Analog I/O configuration
EM30 – Rev.03 -EN- SOFT Rev. 1.1x
© 2017-06-KPP-EURADRIVES EUROPE GmbH
- 47 -
Analogue output configuration
AO1, AO2
F423
Signal type configuration output
AO1
current/voltage signal
Selection: 0=0…5V
1=0…10V, 0…20mA *
2=4…20mA *
Default setting: 1
F424
Inverter output frequency assigned to
minimum output signal on
AO1
Range: 0.0…F425
Default setting: 0.05 Hz
F425
Inverter output frequency assigned to
maximum output signal on
AO1
Range: F424…F111
Default setting: 50.00 Hz
F426
Gain factor
AO1
Range: 0…120%
Default setting: 100
*) The DIP-SWITCH U/I must be set, to get current signal on AO 1 output – see chapter 5) Control hardware and IO/
channel configuration
F427
Signal type configuration output
AO2
current signal only
Selection: 0=0…20 mA
1=4…20mA
Default setting: 0
F428
Inverter output frequency assigned to
minimum output signal on
AO2
Range: 0.0…F429
Default setting: 0.05 Hz
F429
Inverter output frequency assigned to
maximum output signal on
AO2
Range: F428…F111
Default setting: 50.00 Hz
F430
Gain factor
AO2
Range: 0…120%
Default setting: 100
F431
Assignation of operating
parameters
to
AO1
Selection: 0=Motor frequency
1=Motor-current normalized on 2xI-n)
2=Motor-voltage (normalized on 230/400V)
3=AI1
4=AI2
5=Impulse input
6=Torque – normalized to m-n
7=Set via MODBUS
8=Target frequency
9=Calculated speed
10=Torque (motoric)
Default
setting: 0
F432
Assignation of
operating parameters
to
AO2
Default
setting: 1
Assignation motor current: The full range corresponds to 0…2x inverter rated current
Assignation motor voltage: The full range corresponds to the inverter rated voltage (230V/400V)
F433
Multiplier for motor voltage meter
Range: 0.01…5* rated value
Default setting: 2.0
F434
Multiplier for motor current meter
Default setting: 2.0
F437
Filter factor analogue output
Range: 1....100
Default setting: 10
Pulse output
DO1
:
Digital output terminal DO1 can be programmed via F303 as pulse signal output – configuration is made in a
similar way, as for analogue outputs
F449
Max. frequency pulse output
DO1
Range: 0.00…50.00 kHz
Default: 10.00 kHz
F450
0-point offset (%)
Range: 0.0…100.0 %
Default: 0.0%
F451
Multiplier
Range: 0.00…10.00
Default: 1.00
F453
Assignation of
operating parameters
to
DO1
Selection:0=Motor frequency
1=Motor-current normalized on 2xI-n)
2=Motor-voltage (normalized 230/400V)
3=AI1
4=AI2
5=Impulse input
6=Torque – normalized to m-n
7=Set via MODBUS
8=Target frequency
9=Calculated speed
10=Torque (motoric)
Default setting: 0