1) Common installation rules and safety information regarding EURA EM30 inverters
Handling, transportation and storage
Inverter components may become damaged and insulating distances
may be reduced, as a result of improper transportation, handling or
storage of the drive.
DANGER
In this case, the inverter does not anymore comply with product
specific standards and rules, and it is not allowed to place it into
operation.
Therefore it is mandatory, to check the inverter for mechanical
integrity, before installation and operation.
The inverter may contain components, sensitive to electrostatic
discharge. Therefore avoid, touch components inside the drive.
It is recommended to store the inverter, using the original box.
If inverters are stored or out of use for more then one year, DC
capacitors may lose their capacity. Please contact the inverter
manufacturer for reformatting procedure
Installation of the inverter
DANGER
Frequency inverters EP66 must be mounted, following instructions in
chapter
: Inverter mounting
Only fixed installation is permitted.
Follow all effective standards and rules for correct grounding!!
All minimum distances to other inverters or components are to
respect. Minimum distances are reported later on this manual.
Allow adequate air circulating, especially, in case of vertical mounting,
one on top of the other.
Use proper shielded cables, for inverter control signals and feed back
signals
Intrusion of dust, liquids, water, steam and aggressive gases must be
excluded
Attention on adequate heat exchange of the cabinet
Use of the inverter in explosion risky area is not allowed
Electrical wiring of frequency inverters
Attention: The entire plant must be disconnected from power,
crosschecked for loss of voltage and locked before starting any
work
DANGER HAZARDOUS
CAPACITOR CHARGE
The discharge time of the internal DC-LINK capacitors
may take up to 5 minutes, it is not allowed to open the
enclosures or to do any maintenance work during
discharge cycle!!