9) Parametergroup 200: Inverter control
EM30 – Rev.03 -EN- SOFT Rev. 1.1x
© 2017-06-KPP-EURADRIVES EUROPE GmbH
- 39 -
F209
“STOP” mode selection
Selection: 0: STOP controlled by deceleration ramp
1: Free-stop (uncontrolled)
2: STOP with DC injection
Default setting: 0
If
F208=1:
STOP command disables the final stage, motor stops uncontrolled by inertia
If
F208=2:
STOP wit DC brake function (defined in
F600
,
F603, F605, F656)
ATTENTION: In DC brake mode all kinetic energy will dissipate in the rotor. Cyclic use of DB braking, or braking of high
inertial mass may overheat the motor.
F210
Frequency resolution with
motorpotentiometer control via keypad/terminals
Range: 0.01 - 2.00 Hz
Default setting: 0.01 Hz
F211
Variation speed in motorpotentiometer
control mode via keypad/terminals
Range: 0.01 - 100.0 Hz/sec.
Default setting: 5.00 Hz/sec
If
F203=0/5:
Inverter starts with initial frequency
F113
(memory with F203=0) –
F220=1,
to memorize with power-down too
F212
Status memory with (208=3)
Selection: 0: deactivated
1: activated
Default setting: 0
If activated, after power down or reset, the inverter will restart with the same status, as before (the previous start impulse
forward/reverse was memorized)
F213
Autostart after power-down
Selection: 0: deactivated
1: activated
Default setting: 0
F214
Inverter-Error AUTO-RESET
Selection: 0: deactivated
1: activated
Default setting: 0
F215
Power-on Autostart delay (sec.)
Bereich: 0.1…3000.0 sec.
Default setting: 60.0
F213=1
will force the inverter to restart automatically in case of power off. On power-on, the inverter will restart with the same
conditions, as before (frequency/direction).
F215
defines the delay time for power-on autostart.
Power-on autostart works only with
F208=0
(dynamic start command)
F214=1
will cause an automatic reset in case of inverter error.
F217
is the delay time for error-reset, while
F215
works as delay
time for restart after error-reset.
Autostart is performed only if error occurs during START condition (motor running), in case of STOP condition, only error-reset
will be done.
In case of deactivated automatic error-reset, manual reset (keypad/terminal signal) must be done
F216
Number of error-reset tentative
Selection: 0 - 5
Default setting: 0
F217
Delay time for error-reset
Range: 0.0 - 10.0 sec.
Default setting: 3.0 sec.
WARNING: Activation of AUTOSTART and/or AUTORESET may result in unexpected START up of the drive system!!
F219
EEprom write protection under MODBUS control
Selection: 0: deactivated
1: activated
Default setting: 1
Please note that
F219
, the EE-prom write protection it is activated by default (to prevent EE-prom from getting destroyed due to
repetitive write operations). With this configuration all data sent by MODBUS are stored in the RAM only and get lost after
power-down.
If inverter works with continuously varying parameter values, like speed reference, it is recommended, to work in the RAM only.
F220
Memory function for speed and rotation direction in case of
power-down
Selection: 0: deactivated
1: activated
Default setting: 0
Valid in case of internal speed reference (
F113), (F155 – F156)
F224
F-min handling
Selectionl: 0: f<F-min: STOP
1: f<F-min: RUN with F-min
Default setting: 0
F277
Acceleration time 3 (sec.)
Range: 0,1 – 3000sec.
Default setting:
depending on
inverter size
F278
Decelaration time 3 (sec.)
F279
Acceleration time 4 (sec.)
F280
Decelaration time 4 (sec.)