For Support Contact   +46 8 25 28 75, [email protected] or +61 2 9956 7377, [email protected] 

 

COMMAND 

ACTION 

RESPONSE/NOTES 

ET-SSP=PhNo1, 
PhNo2,…,PhNo5 

Set SMS Alarm Phone Numbers 

All numbers must be entered, if less than 5 numbers 
enter 

,’s with no spaces between until all 5 slots are 

completed e.g. 

ET-SSP=XXXXXXXXXX,,,, 

 

Note: you cannot add/or remove phone numbers to 
the unit in this manner as the unit will not 
necessarily have the correct corresponding entry in 
the individual I/O settings. 

 

Only use to change existing phone list, so if three 
number in an already existing list then replace with 3 
numbers 

ET-SL=10 

Set SMS sending limit 

 

 
 

Pulse input commands 

 

COMMAND 

ACTION 

RESPONSE/NOTES 

ETSPI=0,0 

Set pulse values to 0 and reset all logged 
channels. 

 

ET&P 

Show pulse status 

 

 
 

Internet commands 

 

COMMAND 

ACTION 

RESPONSE/NOTES 

ET-IC 

Connect to an ISP 

 

ET-IP1=ip:port 

Set Internet Service Parameters 

ip = remote server IP-address 

port = remote port 

1 for IP-address 1, 2 for IP-address 2 etc. 

ET-IDC 

Disconnect to Internet and the Socket server 

 

ET-ILP=port 

Local port No 

 

ET-ISC 

Close a Socket 

 

ET-ITP 

Internet Transparent mode 

 

Summary of Contents for 71610

Page 1: ...ounted including wall mount bracket Integrated 2G 3G 4G wireless modem Customized SMS alerts LED indicators for cellular signal quality and communication status Pre configured for the most common sens...

Page 2: ...ation Tool 15 Installation 15 Using the Right Version of the Configuration Tool 15 Using the Configuration Tool 16 Saving reading and writing configuration files 17 General Settings tab 18 Phone numbe...

Page 3: ...wer SWT5 28 What you should know about the Low Power Mode 29 Heart Beat package 30 Communication tab 32 Remote Server 32 ISP Dial up Login 32 Connected to ISP or Server 33 Firewall 33 Internal Serial...

Page 4: ...ing Diagram 44 Configuration Tool Settings 45 Tank Level monitoring with Rochester Gauge 46 Water Electrical meter measurement 47 Pressure Sensor 48 Control Via ET Commands 49 General commands 49 I O...

Page 5: ...with SCADA systems or via simple user friendly SMS commands The DeltaBlack can be delivered with a pre provision world wide SIM card Connect the sensors turn on the power and log into ETM s IoT Cloud...

Page 6: ...900 1700 2100 AWS 1800 1900 2100 and 2600 MHz bands 1 2 3 4 5 7 8 12 18 19 20 28 UMTS 800 850 900 1700 2100 AWS 1800 1900 and 2100 MHz bands 1 2 4 5 8 9 19 GPRS 850 900 1800 and 1900 MHz Casing Alumin...

Page 7: ...ded Power supply specifications are shown below ITEM DESCRIPTION SOCKET Voltage 6 35V Power Consumption 600 mA rated 150 mA transmitting 35 mA idle Case Casing DeltaBlack features an aluminium casing...

Page 8: ...nalogue Input 0 2 5V Max Input 50VDC CH3 Digital Input LL 0 5V HL 2 5V Max Input 50VDC Digital Output LL0V HL3V 0 1mA Pulse Input LL 0 5V HL 2 5V Max Input 50VDC Analogue Input 0 2 5V Max Input 50VDC...

Page 9: ...5V Max Input 50VDC Digital Output LL0V HL3V 0 1mA Pulse Input LL 0 5V HL 2 5V Max Input 50VDC CH2 Analogue Input 4 20mA Max Input 50VDC CH3 Analogue Input 4 20mA Max Input 50VDC CH4 Analogue Input 4 2...

Page 10: ...ort The RS232 Port is the primary interface for the configuration tool software ET AT commands can also be used to communicate with the terminal The RS232 interface is implemented as an 8 pin RJ45 soc...

Page 11: ...in DO 0 or 3 3V 10uA ON Ch 3 AI 4 20 mA SW4 OFF Ch 4 DI default high dry contact to ground or LL 0 5V HL 2 5V AI 0 to 2 5V Pulse in DO 0 or 3 3V 10uA ON Ch 4 AI 4 20 mA SW5 OFF Ch 2 DI Default high dr...

Page 12: ...unit supports both 3V and 1 8V SIMs Any SIM card used needs to be correctly provisioned for the services and network upon which it is intended to be used SIM Pin If the SIM used has a PIN either The u...

Page 13: ...s Bottom row GREEN LED 1 FUNCTION Slow Flash 500ms On 500ms Off Searching for mobile network Double Flash 3s Off 100ms ON 100ms OFF 100 ms ON Active 2G network connection Triple Flash 3s OFF 100ms ON...

Page 14: ...For Support Contact 46 8 25 28 75 sales etmiot se or 61 2 9956 7377 sales etmiot com au Signal strength levels...

Page 15: ...rectory as the configuration tool for continued easy operation of the tool Using the Right Version of the Configuration Tool When the unit starts up and is connected to a terminal window and Escape is...

Page 16: ...d 8 NOTE You can also check the tick box Send ESC on SYSTEM START the Configuration Tool to will automatically send an ESC character when it sees the SYSTEM START message in the bottom right hand corn...

Page 17: ...t opened an existing configuration file or performed a read operation The button Com3 115200 OPEN can be used to control whether or not the communications port is opened you must have the communicatio...

Page 18: ...nal number in any entry e g 4670xxxxxxx Analogue Values Default presented in mV Analogue values sent by TCP UDP or SMS are presented in mV The range of each analogue input is 0 2500 mV Scaled with cal...

Page 19: ...ctive for more than x minutes the unit will restart Password To set a password use the ET command ETSPW see Control via ET commands later in this document This password must then be entered in this fi...

Page 20: ...h or Low to the alert message This is enabled by default Append Unit ID allows you to choose whether or not to add the Unit ID to the alert message Real Time Clock Sync Select how the RTC is synchroni...

Page 21: ...sent when a circuit involving the actual I O pin changes from close to open from grounded to not connected The I O is indicating high signal when not connected pull upped See later in this document fo...

Page 22: ...for internal sending of an ET command which could be used to change a timer or turn on off an output as the result of an alarm trigger or an input Alarm delay Waits a specified time before the alarm...

Page 23: ...set point which would otherwise cause multiple alarms to be sent For channels 5 6 and 7 the options for sending ET commands are not available The unit can send an alarm when the unit s supply voltage...

Page 24: ...alarm message for low battery level Power in Low Level If the supply voltage falls below this value the unit will turn into shutdown mode Here the cellular module will be turned off and only the proce...

Page 25: ...in mV uses the 21 format while Scaled with calibrated values uses the 22 format Send to server for logged data Activate and send data to server If checked connect to ISP at start up also activates Al...

Page 26: ...om au SWT3 This time sends the current values as configured The sending port will be 2800 SWT4 This time sends the current values as configured The sending port will be 2880 The data types are defined...

Page 27: ...from closed circuit 0 5V to open circuit 2 5V High to low Counts a pulse on transition from open circuit 2 5V to closed circuit 0 5V Both Uses both Low to high and High to low The pulse register can...

Page 28: ...d data scaled according to settings in the Channel Scaling tab 32 will send extra control parameters Monitoring data SWT3 This will send certain types of data through port 2800 depending on your choic...

Page 29: ...urned on will save power Wake up if Send Req The unit wakes up if there is a send request trigged by another timer SWT2 3 or 4 If not checked the unit will only wake up according to the SWT5 time inte...

Page 30: ...l between sends This value must be equal to or larger than the SMS Poll Period under the General Settings tab SMS sending 30 format Unit ID sends an SMS formatted as 30 every X minutes to provide an i...

Page 31: ...lures before ISP disconnect means that if an initial data send cannot be initiated then a ping failure is registered After a configured amount of failures the ISP considered to be disconnected and the...

Page 32: ...The IP address and port is entered as 54 77 219 177 8608 for IP address 54 77 219 177 and port 8608 Note Do not enter in the format 054 077 219 177 8608 You may need to forward the chosen port to a se...

Page 33: ...ls has been reach it will try to connect via 2G If the max reconnection using 2G trials has been reach it will try to connect via 4G again If a successful connection has been established the same acce...

Page 34: ...ce connected to the port For Flow Control currently only CTS is supported For a baud rate of 9600 57600 or 115200 the MCU will use a feature called auto baud to adjust to the correct baud rate For oth...

Page 35: ...limited amount of data can be stored in the memory during periods of network outages or if sleep mode is used Channel values Latest value for all input channels Alarm History Viewer List of alarms se...

Page 36: ...nit might be busy and fail to execute the command wait and try again Make sure to set the baud rate to 115200 for the escape sequence to work You do that by clicking the Set COM Port button and choose...

Page 37: ...77 sales etmiot com au Set RTC This button is used to set the Reference Date and Time Reprogram using CSD If your SIM has been provisioned for Circuit Switched Data then it is possible to dial into th...

Page 38: ...s the resolution of 4096 steps Example We have a temperature sensor specified to give 1000 mV at 10 C and 2000 mV at 20 C If we are using an analogue channel configured for 0 2500 mV this corresponds...

Page 39: ...9956 7377 sales etmiot com au APPLICATION EXAMPLES This section includes a few examples of how the devices can be electronically wired as well as a couple of software configurations for different type...

Page 40: ...om au Configuration Tool Settings 1 Enter Phone Numbers and Unit ID in the General Settings tab 2 In Data Transfer Logging Times Set Data Logging to On Timed Event on I O1 and both checked under Pulse...

Page 41: ...For Support Contact 46 8 25 28 75 sales etmiot se or 61 2 9956 7377 sales etmiot com au TEMPERATURE ALARM Wiring Diagram...

Page 42: ...represents 85 C which corresponds to 2500mV Therefore the 1500mV trip point equates to 22 5 C in the example below a restore message will be sent when the temperature drops back below 22 5 C Note con...

Page 43: ...For Support Contact 46 8 25 28 75 sales etmiot se or 61 2 9956 7377 sales etmiot com au PUMP CONTROL...

Page 44: ...For Support Contact 46 8 25 28 75 sales etmiot se or 61 2 9956 7377 sales etmiot com au TANK LEVEL MONITORING WITH 4 20mA SENSOR Wiring Diagram...

Page 45: ...1 Enter Phone Numbers and Unit ID in the General Settings tab 2 In Data Transfer Logging Times Set Data Logging to On Timed and check the box Toggle SensFeed ch30 Check Input Ch 3 I O3 and make sure t...

Page 46: ...For Support Contact 46 8 25 28 75 sales etmiot se or 61 2 9956 7377 sales etmiot com au TANK LEVEL MONITORING WITH ROCHESTER GAUGE...

Page 47: ...For Support Contact 46 8 25 28 75 sales etmiot se or 61 2 9956 7377 sales etmiot com au WATER ELECTRICAL METER MEASUREMENT...

Page 48: ...For Support Contact 46 8 25 28 75 sales etmiot se or 61 2 9956 7377 sales etmiot com au PRESSURE SENSOR...

Page 49: ...minal ETI Send DeltaBlack information ID ID string RTC Real Time Clock Date and Time REFDATE Reference date Day counter TOTAL Total time since start RSTIN Time to SW reset RC SW PU Reset counter SW Po...

Page 50: ...n scaled value otherwise raw voltage input ETRAIA Read all analogue inputs ETS X AI Set I O pin No X to analogue input Several pins can be combined i e ETS 3 AI 4 DI etc ETS X DI Set I O pin No X to d...

Page 51: ...n the individual I O settings Only use to change existing phone list so if three number in an already existing list then replace with 3 numbers ET SL 10 Set SMS sending limit Pulse input commands COMM...

Page 52: ...minute p periodicity min ETSWT Show wakeup timers and tasks ETSUI xxx Set User ID Max 40 characters ETSC1 Set communication direction 0 shutdown com device low power mode 1 open communication Modem P...

Page 53: ...tteknik AB Ekbacksv gen 32 SE 168 69 Bromma Sweden Tel 46 0 8 25 28 75 Fax 46 0 8 80 11 10 Email sales etm se Web www etm se ETM Pacific Pty Ltd Suite 6 273 Alfred Street North Sydney NSW 2060 Austra...