For Support Contact +46 8 25 28 75, [email protected] or +61 2 9956 7377, [email protected]
ETSC1
Change to AT-command mode
ETSPW=xxxxxxx
Set a password for the configuration tool
Use up to 7 characters.
ETPW=xxxxxxx
Enter the password
The unit will be ready for configuration. It is locked
again after 10 minutes, and at reset.
I/O commands
COMMAND
ACTION
RESPONSE/NOTES
ETRIS
Show status/value of each I/O
1:DI,1 = I/O 1 digital input
2:DI,1 = I/O 1 digital input
3:DO,1 = I/O 3 digital output, level 1 (high, see
below)
etc.
ETRAIX
Read A/D input
X is AI No, ETRAI3 reads analogue input 3.
If configured for scaled values, this will return scaled
value otherwise raw voltage input
ETRAIA
Read all analogue inputs
ETS(X:AI)
Set I/O pin No X to analogue input
Several pins can be combined, i.e. ETS(3:AI,4:DI)
etc.
ETS(X:DI)
Set I/O pin No X to digital input
ETS(X:DO=0)
Set I/O pin No X to digital output, set pin level
(0=low, 1=high)
Low DO status is <0.5V 0.1mA, High DO Status is
>2.5V 0.1mA. External Circuitry capable of detecting
these signals is required to switch external devices
ON/OFF.
ETS(X:DO=0)TAY
Set I/O pin No X to digital output, set pin level for
a specified time period.
Time specified as Y seconds, after this the level
reverts to the other option (low/high).
ETSAC=
n,p1,p2,timeout,unit
Set A/D calibrating parameters
n = A/D channel number
p1 = 1st input point
p2 = 2nd input point
timeout in seconds, default 10 s
unit = mV, V, M, dgC, mA, A etc., default mV
SMS commands