6 / 16
Advance Set-up Menu:
PARAMETER
DESCRIPTION
RANGE
DEFAULT
$$
.
Mains Connection
0 = Three-Phase
1 = Single-Phase
0 … 1
0
$$
.
*
Sense of CT current
1 = CT on L1 Direct
2 = CT on L1 Inverse
1 … 6
1
3 = CT on L2 Direct
4 = CT on L2 Inverse
5 = CT on L3 Direct
6 = CT on L3 Inverse
$
.
Frequency
1 = 50 HZ
2 = 60 HZ
1 … 2
1
$
.
Serial interface TTL
0 = Disable
1 … 99 = Enable
0 … 99
1
**
$
.
Temperature Alarm
0 = Disable
35 … 158 = Enable
0 / 35 … 158
45 (°C)
$
.
Temperature scale
0 = °C
1 = °F
0 … 1
0
$
.
Alarm THD (%) I
5 … 200
120
$
.
THD(%) Delay on (seconds)
1 …
600
5
$
.
Alarm relay
(see Table pag.10)
0 = None
1 = All
2 =
$$
.
++8
3 =
$$
.
//8
4 =
$$
.
++,
5 =
$$
.
//,
6 =
$$
.
++&
7 =
$$
.
//&
8 =
$$
.
77+
9 =
$$
.
&&6
0 … 9
1
$
.
Time to switch off all the capacitors because of low current (seconds).
1 … 240
120
$
.
Min Temp. to switch off the fan relay output. (if selected °F set the right value)
1 … 240
30
$
.
Max Temp. to switch on the fan relay output. (if selected °F set the right value)
1 … 240
50
$
.
Mains Three Phase Voltage.
220 … 440
with step of 5
400
$
.
Fixed step selection (0=none)
0 … 12
0
$
.
0 = kvar with subtraction fixed step
1 = Real kvar
0 … 1
1
$
.
Serial Protocol Type
0
Proprietary
9600 Bds
EVEN
1 Bit Stop
0 … 15
0
1
Modbus
19200 Bds
EVEN
1 Bit Stop
2
Modbus
9600 Bds
EVEN
1 Bit Stop
3
Modbus
4800 Bds
EVEN
1 Bit Stop
4
Modbus
2400 Bds
EVEN
1 Bit Stop
5
Modbus
1200 Bds
EVEN
1 Bit Stop
6
Modbus
19200 Bds
ODD
1 Bit Stop
7
Modbus
9600 Bds
ODD
1 Bit Stop
8
Modbus
4800 Bds
ODD
1 Bit Stop
9
Modbus
2400 Bds
ODD
1 Bit Stop
10
Modbus
1200 Bds
ODD
1 Bit Stop
11
Modbus
19200 Bds
NONE
1 Bit Stop
12
Modbus
9600 Bds
NONE
1 Bit Stop
13
Modbus
4800 Bds
NONE
1 Bit Stop
14
Modbus
2400 Bds
NONE
1 Bit Stop
15
Modbus
1200 Bds
NONE
1 Bit Stop
16 Proprietary
9600 Bds
NONE
1 Bit Stop
17 Proprietary
4800 Bds
NONE
1 Bit Stop
$
.
Anti-Hunting
0 = Disable
0.90 …
-0.95 = Enable
0 / 0.90 …
-0.95
0
$
.
Threshold for Cos
M
alarm 0 = Disable
0.50 … 0.95 = Enable
0 / 0.50 … 0.95
0
$
.
Delay between steps
Switch-ON / Switch-OFF (in sec. with step of 0.1)
1.00 … 5.00
1.00
*
When the
$
.
value is displayed, by pressing together
and
, the updated Cos
M
it’s immediately shown.
**
The values 1 to 99 indicate the device number when the
units are connect on a serial interface, the values 100 to 199 aren’t used.
5.3 TO SET DEFAULT PARAMETERS:
- In
$
.
parameter, press all buttons together
for 5 seconds, on display will shows
6$8
Now the device will restart.
ATTENTION:
All settings made on the device will be lost and all steps will be restored to default setting.
ETI Elektroelement d.d. - Slovenija
Tel.: 03/56-57-570- Fax: 03/56-74-077
www.eti.si - [email protected]