background image

  

2 / 16

1 - BUTTONS  AND INDICATION LEDs:

1

.

1  Indication LEDs

- Inductive Load.

- Capacitive Load.

- External Temperature (internal temperature sensor).

- Manual Operation Mode of the output relays.

- Automatic Operation Mode of the output relays.

- Phase Main Input Voltage.

- Phase Load Current.

- Needed kvar to achieve the Cos

M

adjustment.

- Cos

M

setting for the installation.

- Total Harmonic Current Distortion in %.

- On delay timer to switch the capacitors bank.

1.2  Buttons :

- Button selection for the operation mode , Manual or Automatic.

- Measurements Menu ( V, A, kvar, Cos

M

, THD, Sensitivity )

- Selected Value Decrease.

- Selected Value Increase.

2 - DESCRIPTION:

Control and digital Cos

M

regulation device with accurate and reliable Cos

M

readings, except possible errors deriving from 

ageing of electronic components.
By the mean of particular devices and algorithms, the instrument, controls even electric lines with an high harmonic contents.
By calculating reactive power, it allows to intervene to connect the capacitor banks, which permits their best utilization both in 
number of operations and in equal rating of the capacitor banks.

3 - OPERATION:

> Device model:

At the switching on, for one second, type of device it’s displayed the in the following way.

BOX

Model Type

Display LED

Steps

> Output steps switching on test:

The parameters 

33

.

to

3

.

must be programmed first (5.1 - Basic Set-up Menu).

Pressing button 

or 

the respective outputs and the LED will be activated, letting you test the connections.

96x96

144x144
144x144

PFC6DA

PFC8DB

PFC12DB

06

00

.

6

00

.8

0

.

12

06
12

ETI Elektroelement d.d. - Slovenija

Tel.: 03/56-57-570- Fax: 03/56-74-077

www.eti.si - [email protected]

Summary of Contents for 004656570

Page 1: ...Y SET UP Pg 9 10 OPERATION MODE Pg 9 11 ALARMS TABLE Pg 10 12 TECHNICAL DATA Pg 11 13 TERMINAL CONNECTIONS Pg 15 14 DIMENSIONS Pg 15 AVAILABLE OPTIONAL COMMUNICATION MODULE PC USB RS485 TTL ORDER CODE...

Page 2: ...cept possible errors deriving from ageing of electronic components By the mean of particular devices and algorithms the instrument controls even electric lines with an high harmonic contents By calcul...

Page 3: ...ram Q1 The installer has to provide an external disconnection device this breaker has to be easily reachable and identified as disconnection device The value has to be calculated according to the T1 u...

Page 4: ...means you need to set the value of the primary CT a Press the button to show the parameters value 3 b Press the button to show the parameters value c Press the button to increase or the button to decr...

Page 5: ...eans the alarm relay normally energized that is closed contact in the absence of alarm Pressing again the function is inverted and display show 1R 5 2 ENTER THE ADVANCED MENU a The controller must be...

Page 6: ...Modbus 4800 Bds EVEN 1 Bit Stop 4 Modbus 2400 Bds EVEN 1 Bit Stop 5 Modbus 1200 Bds EVEN 1 Bit Stop 6 Modbus 19200 Bds ODD 1 Bit Stop 7 Modbus 9600 Bds ODD 1 Bit Stop 8 Modbus 4800 Bds ODD 1 Bit Stop...

Page 7: ...or to enter in alarm s parameter shows the G X p Press the button for to enter for set the value q Press the button to increase or the button to decrease the value r Press the button for to enter in a...

Page 8: ...ORD Default password is and not active as default a The controller must be set on MANUAL operation and all capacitors must be OFF b Press the button for 5 seconds c The display will show 6 7 d The LED...

Page 9: ...e decimal point on first digit from left is flashing this is because the system working as Generator and the sense of current is inverted verify correct CT connection or modify parameter b Press the b...

Page 10: ...play will show the Total Harmonic Current Distortion in In Manual Mode press together and the LED blink and the display will show the maximum THD value 9 COSM M SET UP AND SENSITIVITY SET UP 9 1 CosM...

Page 11: ...eps to be examined 4 If the last step is programmed as Alarm relay then the relay can not be driven manually Note During Manual operation the device controls the reconnection time of the capacitors sa...

Page 12: ...perature 10sec The temperature refers to set value Display 27 alternated with CosM value 7 THD I 5sec When the THD is higher than the value set on par 7 alternated with THD 36 Set up parameters error...

Page 13: ...10A 10A Insulating Category Rated Voltage VDE0110 C 250 B 400 C 250 B 400 Maximum Switching Voltage 250V 250V Electrical Contact Life 20 x 106 ops 20 x 1006 ops Mechanical Contact Life 100 x 103 ops 1...

Page 14: ...MODEL The 96x96 picture shows the TTL version optional 14 DIMENSIONS 96x96 MODEL FRONT VIEW SIDE VIEW PANEL HOLE 144x144 MODEL FRONT VIEW SIDE VIEW PANEL HOLE ETI Elektroelement d d Slovenija Tel 03...

Page 15: ...ean the device with a soft cloth dampened with water This operation must be done with the instrument switched off and disconnected from any power source ETI Elektroelement d d Slovenija Tel 03 56 57 5...

Page 16: ...16 16 ETI Elektroelement d d Slovenija Tel 03 56 57 570 Fax 03 56 74 077 www eti si eti eti si...