Basic Set-up Menu:
PARAMETER
DESCRIPTION
RANGE
DEFAULT
33
.
Primary current transformer.
The first dot on the display flashes to indicate the scale in thousands.
0 / 5
… 10000
0
3
.
Rated power (nameplate) in kvar of the smallest capacitor bank.
0.01…10000
0.10
3
.
Rated capacitor voltage (nameplate) in volts.
80 … 30000
400
3
.
Reconnection time of the same step in seconds. (Capacitor discharge time)
1 … 600
180
3
.
(LED 1)
Step 1 kvar
0 … 10000
0
3
.
(LED 2)
Step 2 kvar
0 … 10000
0
3
.
(LED X)
Follow the same programming as above, except for the last TWO steps.
0 … 10000
0
3
.
(LED N-1)
Programming of the last before last step. kvar or external fan
(a)
0 ... 10000
))$1
0
3
.
(LED N)
(b)
Programming of the last step. kvar or alarm output
(c)
0 ... 10000
11R$
-
QQF$
0
3
.
Voltage transformer ratio (ex. V
LINE
/ V
SET
= 500 / 400 = 1.25)
0.40 ... 100
1.00
(a) External fan:
press the button
until the display shows
)$1
The temperature operation control should be set on the Advance Menu
$
.
and
$
.
(b) Last step:
it can be 04/06/08/12 depending on the version
(not present for DPFC04A model).
(c) Alarm output:
when the display shows
, pressing the
key, the letters
QF$
appears (normal close alarm)
which means the alarm relay normally energized that is closed contact in the absence of alarm.
Pressing again, the function is inverted and display show
1R$
5.2 ENTER THE ADVANCED MENU:
a) The controller must be set on MANUAL operation and all capacitors have to be disconnected.
b) Press the button
for 5 seconds.
c) The display will show
6(7
d) The LED
and
will flash with intermittence of 500ms.
e) Press both buttons together
and
for 2 seconds until the display shows
67
.
$
f) Press the button
to show
$
.
, press again for the parameters value.
g) Press the button
to increase or the button
to decrease the value.
h) Press the button
to advance to the next programmed parameter, press again to show the parameter value.
i) Press the button
to return on the programmed parameter.
j) Proceed and program all parameters until the last
$
.
k) After last parameter value press the button
to save the data, display will shows
6$8
and exit the Advance Menu.
All LEDs will flash for a few seconds.
l) If the display shows
(55
, it means that an error has happened and was not possible to save the data.
Therefore it will be necessary to program again all the parameters on the Advance Menu.
For a quick exit from the menu, press
for 3 seconds until display shows
6$8