11 - ALARMS TABLE:

1.

In manual mode the alarms are just a display indication.

2.

Pressing the 

button the visual alarm can temporarily be cancelled, and the readings can be shown to verify

     the causes of the alarms.

     If, for 30 seconds no button is pressed, the visual alarm returns until its removal.

Code

Description

Delay

(default)

Intervention Parameter

Display LED

$$

.

+8

Too high voltage

15min

Voltage over +10% set value.

Display

$

.

++8

VOLTAGE 

LED blink

$

.

/8

Too low voltage

5sec

Voltage under -15% set value

Display

$

.

/8

VOLTAGE 

LED blink

$

.

+,

Too high current

2min

Current exceeds 110%  of the rated value.

Display

$

.

+,

CURRENT 

LED blink

$

.

/,

Too low current

5sec

Current is lower than 2.5% rated value.
If the alarm condition persists for a time exceeding 2 minutes,
then the outputs are disabled.

Display

$

.

/,

CURRENT 

LED blink

$

.

+&

Overcompensation

2min

Capacitors are all disconnected and the Cos

M

is higher than

the preset value.

Display

$

.

+&

alternated 

with Cos

M

value

$

.

/&

Under
compensation

15min

Capacitors are all connected and the Cos

M

is lower than the

preset value.

Display

$

.

/&

alternated 

with Cos

M

value

$

.

27

Over temperature

10sec

The temperature refers to 

$

.

set value.

Display

$

.

27

alternated 

with Cos

M

value

$

.

7+

THD % I

5sec

When the THD is higher than the value set on par. 

$

.

$

.

7+

alternated with

THD%

$

.

36

Set-up parameters
error

-

The set-

up parameters read by the EEPROM aren’t correct.

To restore is necessary the re-set made by the user.

Display

$

.

36

$

.

3&

Adjustment/setting

parameters error

-

The setting parameters read by the EEPROM aren't correct.
The device operates with the default parameters.
There could be error in the calculated measures.

The user can’t do the setting.

It is necessary to return the unit to the manufacturer.

Display

$

.

3&

$

.

38

Parameters error

-

The setting parameters read by the EEPROM aren’t correct

(set Cos

M

, sensitivity, operation mode).

To reset is necessary to contact the manufacturer.

Display

$

.

38

$

.

((

Cancellation
EPROM error

-

Only in the testing phase you can see if the EEPROM 

doesn’t

operates correctly.
Is necessary to contact the manufacturer.

Display

$

.

((

$

.

)5

Frequency error

0

If frequency is out of +-5% of selected value in 

$

.

Check the parameter 

$

.

The frequency is checked only at power on.

Display

$

.

)5

$

.

&6

Low Cos

M

60sec

When the Cos

M

is lower than the value set on par.

$

.

Display

$

.

&&6

alternated with

Cos

M

value

ETI Elektroelement d.d. - Slovenija

Tel.: 03/56-57-570- Fax: 03/56-74-077

www.eti.si - [email protected]

Summary of Contents for 004656570

Page 1: ...Y SET UP Pg 9 10 OPERATION MODE Pg 9 11 ALARMS TABLE Pg 10 12 TECHNICAL DATA Pg 11 13 TERMINAL CONNECTIONS Pg 15 14 DIMENSIONS Pg 15 AVAILABLE OPTIONAL COMMUNICATION MODULE PC USB RS485 TTL ORDER CODE...

Page 2: ...cept possible errors deriving from ageing of electronic components By the mean of particular devices and algorithms the instrument controls even electric lines with an high harmonic contents By calcul...

Page 3: ...ram Q1 The installer has to provide an external disconnection device this breaker has to be easily reachable and identified as disconnection device The value has to be calculated according to the T1 u...

Page 4: ...means you need to set the value of the primary CT a Press the button to show the parameters value 3 b Press the button to show the parameters value c Press the button to increase or the button to decr...

Page 5: ...eans the alarm relay normally energized that is closed contact in the absence of alarm Pressing again the function is inverted and display show 1R 5 2 ENTER THE ADVANCED MENU a The controller must be...

Page 6: ...Modbus 4800 Bds EVEN 1 Bit Stop 4 Modbus 2400 Bds EVEN 1 Bit Stop 5 Modbus 1200 Bds EVEN 1 Bit Stop 6 Modbus 19200 Bds ODD 1 Bit Stop 7 Modbus 9600 Bds ODD 1 Bit Stop 8 Modbus 4800 Bds ODD 1 Bit Stop...

Page 7: ...or to enter in alarm s parameter shows the G X p Press the button for to enter for set the value q Press the button to increase or the button to decrease the value r Press the button for to enter in a...

Page 8: ...ORD Default password is and not active as default a The controller must be set on MANUAL operation and all capacitors must be OFF b Press the button for 5 seconds c The display will show 6 7 d The LED...

Page 9: ...e decimal point on first digit from left is flashing this is because the system working as Generator and the sense of current is inverted verify correct CT connection or modify parameter b Press the b...

Page 10: ...play will show the Total Harmonic Current Distortion in In Manual Mode press together and the LED blink and the display will show the maximum THD value 9 COSM M SET UP AND SENSITIVITY SET UP 9 1 CosM...

Page 11: ...eps to be examined 4 If the last step is programmed as Alarm relay then the relay can not be driven manually Note During Manual operation the device controls the reconnection time of the capacitors sa...

Page 12: ...perature 10sec The temperature refers to set value Display 27 alternated with CosM value 7 THD I 5sec When the THD is higher than the value set on par 7 alternated with THD 36 Set up parameters error...

Page 13: ...10A 10A Insulating Category Rated Voltage VDE0110 C 250 B 400 C 250 B 400 Maximum Switching Voltage 250V 250V Electrical Contact Life 20 x 106 ops 20 x 1006 ops Mechanical Contact Life 100 x 103 ops 1...

Page 14: ...MODEL The 96x96 picture shows the TTL version optional 14 DIMENSIONS 96x96 MODEL FRONT VIEW SIDE VIEW PANEL HOLE 144x144 MODEL FRONT VIEW SIDE VIEW PANEL HOLE ETI Elektroelement d d Slovenija Tel 03...

Page 15: ...ean the device with a soft cloth dampened with water This operation must be done with the instrument switched off and disconnected from any power source ETI Elektroelement d d Slovenija Tel 03 56 57 5...

Page 16: ...16 16 ETI Elektroelement d d Slovenija Tel 03 56 57 570 Fax 03 56 74 077 www eti si eti eti si...

Reviews: