Configuration
28 / 106
– Group functions can be supplemented by the <group offset> func-
tion, which allows light control with fewer presence detectors.
For details see
.
– Group functions can be supplemented by the <Change over groups>
function, which allows light control to be adapted to changing room
situations.
For details see
Application example: Groups for room zones
Explanation: Each presence detector provides individual, presence- and
daylight-dependent light control in its room zone. If no one is present, as
in group 2, the lighting remains switched off.
5.1.3
Open-loop light control - Closed-loop light control
Description
Basically, there are two ways the APC control can influence the lighting:
–
Open-loop control
(the standard case)
How it works: Lighting is regulated to a constant brightness level
depending on the amount of daylight.
Relevant parameter: Brightness setpoint
Technical implementation: Brightness is continuously measured and
compared to the brightness setpoint. Light output is continuously
adjusted so that the difference between the measured brightness
value and the brightness setpoint is minimised.
Light fixture (illuminance in %)
Presence detector (e.g. one APC DALI-2, three BMS DALI-2)
Person present
No person present
|
|
|
|
Gr
QWR
1
Gr
QWR
2
1((
1((
1((
1((
Gr
QWR
3
|
|
|
|
Gr
QWR
4
|
|
|
|