MA
01
994
30
0
EN
Products section
69 / 106
• Use the slider to set the expected amount of daylight in the room
(see table).
The higher the amount of daylight, the more the measured bright-
ness value is corrected downwards to always ensure optimal light
control.
7.8.3
Afterglow
Description
– Afterglow is an additional function for automatic light control or light
control.
– Afterglow starts after the follow-up time of an automatic light control
or light control has elapsed and prevents unwanted darkness.
– During the afterglow duration, light output is controlled to a value
relative to the standard light level. After the afterglow duration has
expired, a separate afterglow time runs.
– If automatic light control would control below the light level in after-
glow, afterglow is not used.
– In case of presence detection during afterglow, the previously used
function is reactivated.
– A light scene can be accessed during afterglow.
Requirements
– Afterglow must be activated. Afterglow is deactivated in the factory
setting.
– The control system is in [Fully automatic] or [Semi-automatic] oper-
ating mode.
– Light output in the previous state is greater than/equal to the light
output when afterglow started.
Expected daylight
Position of the slider
little to no daylight (e.g. north side, no or very
small windows)
towards the moon icon
little to medium amount of daylight (e.g. east or
west side, normal window areas)
between moon and sun icon
a lot of daylight (e.g. south side, many windows or
large window fronts)
towards the sun icon
lx
%
%
t
t
% max.
% min.