Products section
95 / 106
Adjustable parameters
The following situations can be set for the switch position at the button
input:
7.12.6
Actuators
Description
– The APC has an actuator (relay) with two-pole actuator connection
K1/K2 (potential-free, max. 10 A).
– The [Actuators] function can be used for different tasks, depending
on the type of component connected.
– Relay function [Switch lighting]:
The actuator switches depending on the light output of the con-
trol gear. The actuator switches when the current light output
exceeds or falls below the switch threshold (switch-on value or
switch-off value).
– Relay function [Switch HVAC]:
The actuator switches depending on presence detection. The
switch-on delay and the follow-up time after the last presence
detection can be set. Room brightness and light output are not
relevant.
Switch position
Setting value
Effect
open
–
–
closed
Change over group ON
A
closed
switch position is passed to the
<Change over group> function.
Change over group OFF
An
open
switch position is passed to the
<Change over group> function.