MA
01
994
30
0
Overview
12 / 106
Control system/bus system
DALI-2 (IEC 62386)
DALI output voltage
16 V DC
External power supply possible
9.5-22.5 V DC
DALI guaranteed output current
240 mA
DALI maximum output current
250 mA
DALI no-load current
2 mA
DALI quiescent current input
1.9 mA
DALI start-up time
600 ms
Push-button/switch connections
4x (non-floating)
Push-button/switch connections, potential
230 V AC
Switch actuator connection
1x (potential-free)
Switch actuator connection, potential max.
250 V AC / 24 V DC
Switch actuator connection, current max.
10 A
Motion sensor
Principle
Passive infrared (PIR)
Warm-up time
25 s
Detection angle
360°
Detection range transverse ø
8 m – 24 m – 32 m
*
Detection range frontal ø
6 m – 11 m – 11 m
*
Presence range detection range ø
4 m – 8 m – 8 m
*
Max. detection area
50 m
2
– 452 m
2
– 804 m
2
*
Recommended mounting height
3 m – 3 m – 3 m
*
Maximum mounting height
5 m – 10 m – 10 m
*
*
each for model /8 – /24 – /32
Range adjustment
mechanically, by means of cut-to-size lens mask
Light sensor
Light measurement
Mixed light
Brightness range
5-2000 lx
APC10
Summary of Contents for COMPACT APC10 DALI-2