18.5.13. PH
PH: Large temperature differential protection
between water out and water in
Check whether actual temperature
difference between water out and
water in is large than14°C
No
Water in and water out
temperature sensor are
correctly connected and
effectively
Yes
PCB is damaged.
Replace PCB
Correct connect the temperature sensor
or replace temperature sensor
No
Yes
The water flow rate is not sufficient
The water system is blocked
Yes
Check the system and fix the problem
No
The water pump speed is suitable
No
Adjust water pump to high speed suitable
Yes
The additional water pump is not suitable
selected
Select a suitable additional water pump
92