18.5.10 P5
When condenser temperature is over 62
o
C the system will display P5 protection, the ODUs will standby.
When the condenser temperature goes back to normal range, P5 protection finishes and normal operation
resumes.
P5: Condenser temperature protection
Check whether the condenser
temperature is higher than
62°C
Check whether the condenser
temperature sensor is incorrectly
connected or disabled
The ambient temperature is
higher than 48
℃
No
Clean the heat exchanger
Stop the unit and wait for ambient
temperature goes down
No
Replace PCB
Reconnect or replace condenser
temperature sensor
Yes
Yes
Yes
No
Yes
No
No
PCB is damaged
Replace PCB
Low heat exchange efficiency, causes may include
dirty heat exchanger, dirty plate type heat
exchanger, abnormal fan operation, water pump
error, too closed outdoors installation, etc.
Inspect the system and fix the
error
The refrigerant pipe is block, caused by
crushed or bent pipe, blocked EXV valve,
blocked filter, etc.
Inspect the system and fix
the error
Yes
No
85
V.2
Summary of Contents for EMCH-10W/1
Page 16: ...16 6 Diagrama de cables EMCH 07W 1 V 2...
Page 17: ...17 EMCH 10W 1 V 2...
Page 18: ...18 EMCH 12W 1 EMCH 14W 3 EMCH 16W 3 V 2...
Page 29: ...29 V 2...
Page 30: ...30 V 2...
Page 31: ...31 V 2...
Page 33: ...33 12 Vista ampliada EMCH 07W 1 28 1 28 2 28 3 28 5 28 6 28 4 28 7 V 2...
Page 35: ...35 EMCH 10W 1 V 2...
Page 37: ...37 EMCH 12W 1 EMCH 14W 3 EMCH 16W 3 V 2...
Page 110: ...7 Wiring Diagram EMCH 07W 1 15 V 2...
Page 111: ...EMCH 10W 1 EMCH 12W 1 16 V 2...
Page 112: ...EMCH 14W 3 EMCH 16W 3 17 V 2...
Page 123: ...EMCH 12W 1 EMCH 14W 3 28 V 2...
Page 124: ...EMCH 16W 3 29 V 2...
Page 126: ...13 Exploded View EMCH 07W 1 31 V 2...
Page 128: ...EMCH 10W 1 EMCH 12W 1 33 V 2...
Page 130: ...EMCH 14W 3 EMCH 16W 3 35 V 2...