Note:
1. During winter leaving the unit unused, please drain water out completely from unit if no anti-freeze were charged into
pipeline, or keep power on (at standby or off status) and ensure that water is contained inside of unit.
2. When ambient temperature low than 5
℃
, running cooling mode must be charged antifreeze. Refer to the upper table for the
charged volume.
10.2 Fouling Factors
The performance data given refer to conditions with clean evaporator plates (fouling factor=1). For different
fouling factors, multiply the figures in the performance tables by the coefficient given in the following table.
Fouling factors
Evaporator
(m
2
°C/W)
f1
fk1
fx1
4.4×10
-5
-
-
-
0.86×10
-4
0.96
0.99
0.99
1.72×10
-4
0.93
0.98
0.98
f1
: Correction factor of capacity
fk1
: Power input correction factor of compressor
fx1:
Correction factor of total power input
25
V.2
Summary of Contents for EMCH-10W/1
Page 16: ...16 6 Diagrama de cables EMCH 07W 1 V 2...
Page 17: ...17 EMCH 10W 1 V 2...
Page 18: ...18 EMCH 12W 1 EMCH 14W 3 EMCH 16W 3 V 2...
Page 29: ...29 V 2...
Page 30: ...30 V 2...
Page 31: ...31 V 2...
Page 33: ...33 12 Vista ampliada EMCH 07W 1 28 1 28 2 28 3 28 5 28 6 28 4 28 7 V 2...
Page 35: ...35 EMCH 10W 1 V 2...
Page 37: ...37 EMCH 12W 1 EMCH 14W 3 EMCH 16W 3 V 2...
Page 110: ...7 Wiring Diagram EMCH 07W 1 15 V 2...
Page 111: ...EMCH 10W 1 EMCH 12W 1 16 V 2...
Page 112: ...EMCH 14W 3 EMCH 16W 3 17 V 2...
Page 123: ...EMCH 12W 1 EMCH 14W 3 28 V 2...
Page 124: ...EMCH 16W 3 29 V 2...
Page 126: ...13 Exploded View EMCH 07W 1 31 V 2...
Page 128: ...EMCH 10W 1 EMCH 12W 1 33 V 2...
Page 130: ...EMCH 14W 3 EMCH 16W 3 35 V 2...