18.5.15 C8&CP
C8: Water volume protection
CP: Water volume protection in
situation of anti-frozen protection
System water leakage
No
Water pipeline too long and need
an additional water pump
Install a suitable additional
water pump
Fix the leakage and affusion again
Yes
Yes
Water system is blocked
Inspect the system and fix
the problem
No
Yes
The water pump is damaged
No
Yes
Replace water pump
No
The water flow switch is
damaged
Yes
Replace water flow switch
No
PCB is damaged
Replace PCB