18.5.14 Pb
Pb: Anti-frozen protection
Detect actual temperature of inlet water or plate type
heat exchanger: the detected temperature is lower
than 3
℃
in cooling mode or detected temperature is
lower than 5
℃
in heating mode and standby.
No
PCB is damaged
Its normal system protection,
the system will resume when
temperature go up
Yes
No
Check whether temperature sensor of water inlet pipe
or plate type heat exchanger is not effectively
connected or damaged
Yes
Replace or reconnect
temperature sensor
Replace PCB
93
V.2