Remote alarm
Remote alarm terminal only provides passive switching signal.
Current passing through the terminal interface should less than 1.5A, otherwise please use AC contactor to
control load indirectly.
Remote shutdown
If switch is closed, the unit will be stopped forcibly.
Under this circumstance, anti-frozen protection and other protection functions are still effective.
If switch breaks, unit can run normally according settings.
Remote cooling/heating
If switch 2 is closed, the unit will shift to heating mode forcibly;
If switch 2 is break, the unit will shift to cooling mode forcibly.
Note:
1. Remote shutdown and remote cooling/heating is optional function.
Choose this function by DIP switch SW4_1 (SW3_1 for 12/14/16kW) on PCB board. Factory default has not set
remote cooling/heating function.
2. When the remote control and wired controller used at the same time, the unit will carry out the last command of
arbitrary terminal.
3. Remote shutdown has the highest priority. In the status of remote shutdown, other controllers can’t start the
unit.
3 4
Main control board
5
6
SWITCH
SWITCH 2
7
8
48
V.2
Summary of Contents for EMCH-10W/1
Page 16: ...16 6 Diagrama de cables EMCH 07W 1 V 2...
Page 17: ...17 EMCH 10W 1 V 2...
Page 18: ...18 EMCH 12W 1 EMCH 14W 3 EMCH 16W 3 V 2...
Page 29: ...29 V 2...
Page 30: ...30 V 2...
Page 31: ...31 V 2...
Page 33: ...33 12 Vista ampliada EMCH 07W 1 28 1 28 2 28 3 28 5 28 6 28 4 28 7 V 2...
Page 35: ...35 EMCH 10W 1 V 2...
Page 37: ...37 EMCH 12W 1 EMCH 14W 3 EMCH 16W 3 V 2...
Page 110: ...7 Wiring Diagram EMCH 07W 1 15 V 2...
Page 111: ...EMCH 10W 1 EMCH 12W 1 16 V 2...
Page 112: ...EMCH 14W 3 EMCH 16W 3 17 V 2...
Page 123: ...EMCH 12W 1 EMCH 14W 3 28 V 2...
Page 124: ...EMCH 16W 3 29 V 2...
Page 126: ...13 Exploded View EMCH 07W 1 31 V 2...
Page 128: ...EMCH 10W 1 EMCH 12W 1 33 V 2...
Page 130: ...EMCH 14W 3 EMCH 16W 3 35 V 2...