50BF Breaker Failure
There are two sets of breaker failure protection functions. When breaker failure is initiated by an
external trip or other internal logic (user-settable through the output matrix) and the breaker
current still exists, two timers (T1 and T2
–
user-settable) are started. After these timers are timed
out, and if the current still exists indicating a breaker failure, the output of this function is set high.
Use the two outputs of this function to trip another trip coil or the next level of breakers, such as
bus breakers. The breaker failure protection logic diagram is shown below. Phase current
supervision is fixed at 4% of I nominal.
50
–
Breaker Failure Logic diagram
Figure 5.12: Logic Diagram of 50BF Functions
Table 5.13: 50BF Breaker Failure Settings
Setting Description
Range
Function Activation
Enable/Disable
Pick up I
0.05 to 2.0A (1A) / 0.25 to 10.0A (5A)
Pickup Delay 1
0.05 to 999.99 seconds
Pickup Delay 2
0.05 to 999.99 seconds
Summary of Contents for F-PRO 116
Page 2: ......
Page 12: ...1 2 F PRO 116 User Manual D05125R01 20 Figure 1 1 F PRO 116 Relay Function Line Diagram...
Page 16: ...1 6 F PRO 116 User Manual D05125R01 20 Figure 1 4 Ordering Template...
Page 20: ......
Page 30: ......
Page 84: ...7 12 F PRO 116 User Manual D05125R01 20 Figure 7 10 Point Map...
Page 94: ......
Page 96: ......
Page 124: ......
Page 148: ......
Page 149: ...D05125R01 20 F PRO 116 User Manual Appendix H 1 Appendix H Mechanical Drawings H 1 Front View...
Page 150: ...Appendix H 2 F PRO 116 User Manual D05125R01 20 H 2 Rear View...
Page 151: ...D05125R01 20 F PRO 116 User Manual Appendix I 1 Appendix I AC Schematic Drawing...
Page 152: ......
Page 153: ...D05125R01 20 F PRO 116 User Manual Appendix J 1 Appendix J DC Schematic Drawing...
Page 154: ......
Page 155: ...D05125R01 20 F PRO 116 User Manual Appendix K 1 Appendix K Connection Diagram...
Page 156: ......