D05125R01.20
F-PRO 116 User Manual
5-13
Where
θ =
Thermal state in percentage at time t
θ
F
= Final thermal state before disconnection of feeder
I = Effective relay current.
I
θ
= Thermal overload setting
= Thermal time constant in minutes.
The final thermal state
θ
F
for any steady state value of input current can be predicted using the
following formula.
θ
F
= I
2
/I
θ
2
* 100%
49
–
Thermal Overload Logic diagram
Figure 5.11: Logic Diagram of 49 Function
Table 5.12: 49 Thermal Overload Settings
Setting Description
Range
Function Activation
Enable/disable
Thermal Overload Pick up
0.2 to 2.0A (1A) / 1.0 to 10.0 A (5A)
Time constant(
))
0.5 to 100.0 Min.
Negative Sequence Weighing Factor(K)
0.0 to 10.0
Thermal Overload Alarm
Enable/Disable
Pickup % th
50% to 100%
Summary of Contents for F-PRO 116
Page 2: ......
Page 12: ...1 2 F PRO 116 User Manual D05125R01 20 Figure 1 1 F PRO 116 Relay Function Line Diagram...
Page 16: ...1 6 F PRO 116 User Manual D05125R01 20 Figure 1 4 Ordering Template...
Page 20: ......
Page 30: ......
Page 84: ...7 12 F PRO 116 User Manual D05125R01 20 Figure 7 10 Point Map...
Page 94: ......
Page 96: ......
Page 124: ......
Page 148: ......
Page 149: ...D05125R01 20 F PRO 116 User Manual Appendix H 1 Appendix H Mechanical Drawings H 1 Front View...
Page 150: ...Appendix H 2 F PRO 116 User Manual D05125R01 20 H 2 Rear View...
Page 151: ...D05125R01 20 F PRO 116 User Manual Appendix I 1 Appendix I AC Schematic Drawing...
Page 152: ......
Page 153: ...D05125R01 20 F PRO 116 User Manual Appendix J 1 Appendix J DC Schematic Drawing...
Page 154: ......
Page 155: ...D05125R01 20 F PRO 116 User Manual Appendix K 1 Appendix K Connection Diagram...
Page 156: ......