Simple Network Management Protocol [
SNMP
]
Supported Protocols
SNMP versions 1, 2c and 3 are supported, primarily for alarm trap handling. The General EricssonTelevision MIB is also supported.
NOTE: The unit does not support control via SNMP, all remote control is via HTTP or HTTPS.
Operation
The unit’s SNMP functionality can be enabled or disabled, with up to five IP addresses assigned for any SNMP Trap message to be
sent. The default is 000.000.000.000, which causes the SNMP traps to be sent to the last SNMP master. The SNMP community name
can also be set.
The user can control which SNMP traps are generated. The options are;
Start Messages only
Fail and Start Messages only
All Traps
SNMP Interface Parameters
XPO
The unit supports an
HTTP/HTTPS
interface that is
XPO2
compliant for configuration and status monitoring. At least three
simultaneous HTTP/HTTPS sessions can be supported. HTTP access can be enabled or disabled.
Individual parameters can be controlled via XPO2. It does not require the complete XML configuration to be sent to change a single
parameter.
NOTE :
The legacy XPO standard is not supported.
The web pages provide a service orientated control menu structure.
Parameter
Description
SNMP Read Community
The SNMP community name for read access. default = public
SNMP Location
Textual description of the location of the unit
SNMP Contact
Name of the person responsible for this unit
SNMP Trap Community
The SNMP community name for read access. default = private
SNMP Trap Destination
The destination IP address for SNMP trap messages. Up to five
destinations can be defined, but by default none are assigned
SNMP Trap Alarm Level
Defines what events trigger the generation of an SNMP trap
message. The options are:‘Start Messages Only’, i.e. only system
start up events.‘Fail and Start Messages only’ i.e. start-up events
and critical alarms.‘All traps’ i.e. start-up events and all alarms and
warnings.