42
SM-Ethernet User Guide
Issue: 7
6.7.17 Extended speed and torque control
Output assembly object 0x17 (23
10
)
The PLC or scanner must be configured for 6 output bytes (or 3 output words) if this
assembly object is to be used.
Extended control word
The extended control word consists of 2 bytes (16 bits), with only 5 bits of the low byte
used as shown below.
The individual bit functions are described as follows:
Speed reference (
SpeedRef
)
The speed reference word utilises 2 bytes (16 bits) as shown below.
For more information on the setting of the speed reference see section 6.7.26
Table 6.9 Extended speed and torque control
Data word
Function
Word 0
Extended control word.
Word 1
Speed reference (
SpeedRef
).
Word 2
Torque reference (
TorqueRef
).
b15
b14
b13
b12
b11
b10
b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
NetRef
NetCtrl
FaultRst
RunRev
RunFwd
Name
Control Word
Description
RunFwd
b0
Set this bit to command the drive to run in the forward
direction.
RunRev
b1
Set this bit to command the drive to run in the reverse
direction.
FaultRst
b2
A 0 to 1 transition will reset the drive if the drive was in a
trip state.
NetCtrl
b5
Used in conjunction with Pr
6.43
to enable the drive
control word bits b0-b6 and bit 9 (Pr
6.42
).
NetRef
b6
Set this bit to command the drive to use the remote
speed reference value specified in Word 1.
For the drive to run at the speed specified in Word 1, Pr
6.43
must be
ON
and bit 0, bit
7 and bit 8 of the drive control word (Pr
6.42
) must all be set to 1 and the external
hardware enable signal must be present.
For information on the drive control word see Table 6.6
b15
b14
b13
b12
b11
b10
b9
b8
SpeedRef (high byte)
b7
b6
b5
b4
b3
b2
b1
b0
SpeedRef (low byte)
NOTE
NOTE